Transcription of STRAND STRAND HARDWARE LIMITED PH …
1 SH130101 Inst. 4/4 MTBSTRANDPH4303 Timber - RecessedPH4303 Timber - FlushPH4300 Steel - FlushPH4300 Aluminium - SteppedPH4300 Aluminium - FlushPH4304 Floor Striker Floor strikers should be mountedon floor as shown. If aluminium low threshold strips are used thestriker should be notched into aluminium section to comply withcurrent APPLICATIONST ypical door/frame sectionsshowing correct use of strikersA range of PVC-U profile relatedstrikers is also availableDrawings are for guidance only3 - 7 - 6 - 1 - 1 - 4 - 2 - 2 - APH 361 Typical Striker ApplicationsSTRAND HARDWARE LIMITEDS trand House Long St Premier Business ParkWalsall West Midlands WS2 9DY ENGLANDSTRANDSH130101 Inst. 1/4 MTBThe safety features of this exit device are of fundamental importance to ensure its compliance with standard modifications of any kind to the device other than those described in the fitting instructions are permitted.
2 This panic device may be fitted to fire or smoke door : Exit devices shall not include dogging (hold unlocked) when fitted to fire or smoke door assemblies - doggingcan only be used on escape Motorised touch bar Max 1300mmMax 2500mm0425 - 1520 - 11 STRAND HARDWARE LIMITEDS trand House Long St Premier Business ParkWalsall West Midlands WS2 9DY ENGLANDEN1125: 20083-7-7-B-1-4-2-2-B-AIMPORTANT:Before the fitting of Outside Access Device (OAD)or Outside Access Key Switch (KS) onto a door it is important to establish the correct position of the centre mechanism and appropriate 80 For flush applications the strikershould be mounted on frame asshown. 1mm packers areprovided with each strikerFor stepped applications4 - 8mm the striker can be rotated 180 as shown centre mechanism onto door at appropriate touch bar should be positioned between 900 - 1100mmfrom FFL ensuring good contact with centre HOLESFORMECHANISMFFLPH4303 FlushZ This measurement should beestablished before holes aredrilled into door section The fixing plate attached to the touch barmechanism is supplied complete with integral cam.
3 Ensure the cam is positionedas shown before fitting mechanism. Guide the mechanism and connect to theforked plate before fixing with V1 screws. Check operation before Z variesdepending on recessed,flush or stepped recessed situations the PH4303should be turned 90 degrees to doorface as shown - see page 4(striker applications)V1V1V2V1 FIXINGPLATECAMPH4303 RecessedComponentQtyV1 6 V2 2 IAfter completing the cutting of components, re-assemblycentre mechanism to the housing, internal connecting barand touch cap componentsI & II can now besecured using screwsprovidedFor reductions of less than160mm cut touch bar L1 and housing L3 down to size using formula (A)For reductions over 160mmit will be necessary to reduceinternal connecting bar L2 using formula (B) This formulais only for the 1170/1300mm sizes XLCut aluminium profilesusing a circular fixing screws are securelyfixed to the door material.
4 For allglazed aluminium doors, housingbracket HB should extend acrossto the vertical section of door. Alternatively housing bracket HBcan be fixed to midrail. Insert thewiring through hole in centre intodoor = *840mm /*1170mm /*1300mmX = Cutting sizeL = Minimum size* = 700mm(A) X < 160mm: L1 - X, L3 - X (B) X > 160mm: L1 - X, L2 - ( X - 160mm), L3 - XL1 = touch barL2 = internal connecting barL3 = housingL1L2L3 HBHBP lease ensure the formula for reduction of aluminium profiles is followed mechanismcovers in placewith V2 screws andre-tighten M4 screwsM443 hole forwiringthroughinto door sectionMOTOR housed insidetouchbar assemblyto accesscontrolMOTORFor OAD or KS see seperatefitting instructionsSTRANDSH130101 Inst. 3/4 MTBThe safety features of this exit device are of fundamental importance to ensure its compliance with standard modifications of any kind to the device other than those described in the fitting instructions are permitted.
5 This panic device may be fitted to fire or smoke door : Exit devices shall not include dogging (hold unlocked) when fitted to fire or smoke door assemblies - doggingcan only be used on escape Motorised touch bar Max 1300mmMax 2500mm0425 - 1520 - 11 STRAND HARDWARE LIMITEDS trand House Long St Premier Business ParkWalsall West Midlands WS2 9DY ENGLANDEN1125: 20083-7-7-B-1-4-2-2-B-AFix the centre mechanism of touch bar onto door section at appropriate height (touch bar should bepositioned between 900 - 1100mm from FFL) ensuring good contact with centre top and bottom pullmans ensuringgood contact with top and bottom threaded rods to size(X + 15mm & Y + 15mm)Insert threaded rod Binto connector A withlock-nuts C as shown. Push RG rubber grommetsover thread (2 per rod)Insert threaded rodinto riv-nut D of pullmanlatch and connector Aover bush of centremechanism as M4 screws Eto secure connectorin placeAfter final adjustmentsof rods are made, secureall lock-nuts making surethat all of the connectionsare should be taken toensure any lost motion isprevented by adjustmentof threaded rods andlock-nuts.
6 Length of threaded rods: X + 15mmY + 15mmLength of rod covers: X - - : Before the fittingof an Outside Access Deviceonto a door it is important to establish the correct positionof the centre mechanism andappropriate entrypullmans Secure pullmancovers in placewith V2 pullmancovers in placewith V2 screwsFor flush situations strikers should be mounted on frame as shown above. 1mm packersare provided with each stepped applications4 - 8mm the striker can berotated 180 as shown see striker applicationson page 4 for typical + 15mmX + 15mmRGDDDCBX - - rod covers to size(X - & Y - )Push pullman covers intogroove as shown. Position on door and pushmechanism over to hold inplace Secure mechanismcovers in placewith V2 screws andre-tighten M4 screwsM4 MOTOR MOT02 ACCESS CONTROL DEVICEorSWITCHWIRINGDIAGRAMFix the centre mechanism of touchbar onto door section at appropriate height (touch bar should bepositioned between 900 - 1100mm from FFL) ensuring good contact with centre striker if top and bottom pullmans ensuringgood contact with top and bottom threaded rods to size(X + 25mm & Y + 25mm)Insert threaded rod Binto connector A withlock-nuts C as shown.
7 Push RG rubber grommetsover thread (2 per rod)Insert threaded rodinto riv-nut D of pullmanlatch and connector Aover bush of centremechanism as M4 screws Eto secure connectorin placeAfter final adjustmentsof rods are made, secureall lock-nuts making surethat all of the connectionsare should be taken toensure any lost motion isprevented by adjustmentof threaded rods andlock-nuts. Length of threaded rods: X + 25mmY + 25mmLength of rod covers: X - - : Before the fittingof an Outside Access Deviceonto a door it is important to establish the correct positionof the centre mechanism andappropriate rubber washers RG arepushed over threaded rods to prevent any vibration or rattle. Floor strikers should be mounted on flooras shown. If aluminium low threshold strips are used the striker should be notched intoaluminium section to comply with blanking plateBP can be insertedto hold centre latchretracted when notrequired.
8 For theslave leaf of a pairof grooves and voids in aluminium withhard sealant to prevent pre-latching 450 Verticalpullmans RG6144222V1V2 ACEBP1 ComponentQtySecure pullmancovers in placewith V2 rod covers to size(X - & Y - )Push pullman covers intogroove as shown. Positionon door and push mechanismover to hold in place. Secure pullmancovers in placewith V2 screwsRGRGCDCDCCDCBBPV2V2V1V1V1V1V1V1 ABABEY - - + 25mmX + 25mmV2 Secure mechanismcovers in placewith V2 screws andre-tighten M4 screwsM4 STRANDSH130101 Inst. 2/4 MTBThe safety features of this exit device are of fundamental importance to ensure its compliance with standard modifications of any kind to the device other than those described in the fitting instructions are permitted. This panic device may be fitted to fire or smoke door : Exit devices shall not include dogging (hold unlocked) when fitted to fire or smoke door assemblies - doggingcan only be used on escape Motorised touch bar Max 1300mmMax 2500mm0425 - 1520 - 11 STRAND HARDWARE LIMITEDS trand House Long St Premier Business ParkWalsall West Midlands WS2 9DY ENGLANDEN1125: 20083-7-7-B-1-4-2-2-B-ASUPPLY12 - 30v DC12 - 20v AMP-- +Unit should be loop required(not supplied)Do not use power transfercontacts.
9 Trimmer on motor MOT02can be adjusted to allowthe latches to be retractedfor between 4-30 seconds