Technical Data 10638 Effective April 2017E-Rated DIN medium voltage fuses, to 38 kV, 10 to 450 ampsCatalog symbols: 55 GDMSJ_E 55 GFMSJ_E 155 GXQSJ_E 175 GDMSJ_E 175 GFMSJ_E 175 GXMSJ_E 175 GXQSJ_E 258 GDQSJ_E 258 GXQSJ_E 258 GXZSJ_E 38 GFZSJ_E 38 GCZSJ_EDescription:Bussmann series DIN dimensioned E-Rated medium voltage power fuses with striker for indoor use. Available in general purpose ( to kV) and full range ( to 38 kV) :Ratings Volts - 38 kV Amps: 10 - 450 Interrupting rating: 25 - 65 kAAgency information General purpose E-Rated per ANSI ( to kV) Full range E-Rated per ANSI ( to 38 kV)Striker force 50 N (11 Lbs)Recommended fuseclipsSee page 13 for rangeDescriptionCatalog to 200 AEnclosed fuseclip with wingnut tensionerA33574745*Up to 200 AOpen fuseclip with spring tensioner270303* Not sold in and benefits Cool running for lower watts loss 100% X-ray inspected to help assure fuse integrity Striker provides visual indication of fuse operation or a means to activate a remote monitoring systemTypical applications Primary protection for medium voltage transform

Technical Data 10638 Effective April 2017 E-Rated DIN medium voltage fuses, 5.5 to 38 kV, 10 to 450 amps Catalog symbols: • 55GDMSJ_E • 55GFMSJ_E • 155GXQSJ_E • 175GDMSJ_E • 175GFMSJ_E • 175GXMSJ_E • 175GXQSJ_E • 258GDQSJ_E • 258GXQSJ_E • 258GXZSJ_E • 38GFZSJ_E • 38GCZSJ_E Description:

Tags:

  Medium, Trade, Voltage, Fuse, Rated din medium voltage fuses

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Technical Data 10638 E-Rated DIN medium voltage fuses, …

1 Technical Data 10638 Effective April 2017E-Rated DIN medium voltage fuses, to 38 kV, 10 to 450 ampsCatalog symbols: 55 GDMSJ_E 55 GFMSJ_E 155 GXQSJ_E 175 GDMSJ_E 175 GFMSJ_E 175 GXMSJ_E 175 GXQSJ_E 258 GDQSJ_E 258 GXQSJ_E 258 GXZSJ_E 38 GFZSJ_E 38 GCZSJ_EDescription:Bussmann series DIN dimensioned E-Rated medium voltage power fuses with striker for indoor use. Available in general purpose ( to kV) and full range ( to 38 kV) :Ratings Volts - 38 kV Amps: 10 - 450 Interrupting rating: 25 - 65 kAAgency information General purpose E-Rated per ANSI ( to kV) Full range E-Rated per ANSI ( to 38 kV)Striker force 50 N (11 Lbs)Recommended fuseclipsSee page 13 for rangeDescriptionCatalog to 200 AEnclosed fuseclip with wingnut tensionerA33574745*Up to 200 AOpen fuseclip with spring tensioner270303* Not sold in and benefits Cool running for lower watts loss 100% X-ray inspected to help assure fuse integrity Striker provides visual indication of fuse operation or a means to activate a remote monitoring systemTypical applications Primary protection for medium voltage transformers and switch gear Protection of medium voltage feeder circuits Direct OEM replacement fuses for 600 A Square D HVLCC and HVL switches see page 14 for applicable Square D switch catalog symbols and Bussmann series fuse voltage and amp ranges2 Technical Data 10638 Effective April

2 To 38 kV E-Rated DIN medium voltage numbers general purpose versionsCatalog numbersAmpsInterrupting rating (Sym. kA)Dimensions in (mm) (442)2 (51)55 GDMSJ15E1555 GDMSJ20E2055 GDMSJ25E2555 GDMSJ30E3055 GDMSJ40E4055 GDMSJ50E5055 GDMSJ65E6555 GDMSJ80E8055 GDMSJ100E10 (442)3 (76) (537) (89) (442)2 (51) (442)3 (76) (442) (89)175 GXMSJ100E10 (537) (89)175 GXQSJ150E150 Dimensions in (mm)See catalog numbers tables for diameter and length (45) (15)Striker in operated position(striker force 50 N/11 Lbs) (34) (26)3 Technical Data 10638 Effective April to 38 kV E-Rated DIN medium voltage numbers full range versionsCatalog numbersAmpsInterrupting rating (Sym. kA)Dimensions in (mm) (537)2 (51) (537) (89) (718) (89)258 GXZSJ100E10 038 (718)3 (76)38 GFZSJ15E1538 GFZSJ20E2038 GFZSJ25E2538 GFZSJ30E30 Dimensions in (mm)See catalog numbers tables for diameter and length (45) (15)Striker in operated position(striker force 50 N/11 Lbs) (34) (26)4 Technical Data 10638 Effective April to 38 kV E-Rated DIN medium voltage kV time-current curves minimum melting5 Technical Data 10638 Effective April to 38 kV E-Rated DIN medium voltage kV time-current curves total clearing6 Technical Data 10638 Effective April to 38 kV E-Rated DIN medium voltage kV cut-off curvesNotes:1.

3 Curves show extreme maximum values which will not be exceeded under conditions stated in notes 2 and 3 For high values of prospective current, a symmetrical fault gives the highest cut-off current. For low values of prospective current, where there is little or no current limitation, an asymmetrical fault passes the highest peak current. The curves are therefore based upon the degree of asymmetry which gives the maximum cut-off current at any particular value of prospective Curves related to frequency of 60 Hz and a recovery voltage equal to the fuse s rated Data 10638 Effective April to 38 kV E-Rated DIN medium voltage to kV time-current curves minimum melting8 Technical Data 10638 Effective April to 38 kV E-Rated DIN medium voltage to kV time-current curves total clearing9 Technical Data 10638 Effective April to 38 kV E-Rated DIN medium voltage to kV cut-off curvesNotes:1.

4 Curves show extreme maximum values which will not be exceeded under conditions stated in notes 2 and 3 For high values of prospective current, a symmetrical faults gives the highest cut-off current. For low values of prospective current, where there is little or no current limitation, an asymmetrical fault passes the highest peak current. The curves are therefore based upon the degree of asymmetry which gives the maximum cut-off current at any particular value of prospective Curves related to frequency of 60 Hz and a recovery voltage equal to the fuse s rated Data 10638 Effective April to 38 kV E-Rated DIN medium voltage to 38 kV time-current curves minimum melting11 Technical Data 10638 Effective April to 38 kV E-Rated DIN medium voltage to 38 kV time-current curves total clearing12 Technical Data 10638 Effective April to 38 kV E-Rated DIN medium voltage to 38 kV cut-off curvesNotes:1.

5 Curves show extreme maximum values which will not be exceeded under conditions stated in notes 2 and 3 For high values of prospective current, a symmetrical fault gives the highest cut-off current. For low values of prospective current, where there is little or no current limitation, an asymmetrical fault passes the highest peak current. The curves are therefore based upon the degree of asymmetry which gives the maximum cut-off current at any particular value of prospective Curves related to frequency of 60 Hz and a recovery voltage equal to the fuse s rated Data 10638 Effective April to 38 kV E-Rated DIN medium voltage dimensions in (mm) (45) (63) (89) (10) (114) (38) (30) (11) (25) (103)Catalog no. A3354745 not sold in pairsCatalog no.

6 27030314 Technical Data 10638 Effective April to 38 kV E-Rated DIN medium voltage series fuse amp ranges for Square D 600A HVL/CC and HVL switchesCatalog numbersFuse voltage (kV) fuse rangeHVL/CC versionsHVL versionsSingle switch with Square D kV switch HVLCCB14305D HVLCCB20305D 15 kV switch voltsHVLCCA14315D or HVLCCB14315D HVLCCB20315D HVL315 DEG2125-200E HVL315 DEW2125-200E HVL315 DEG110-100E HVL315 DEW110-100E Single switch for cable connection to Power-Dry II, Power-Cast II, and Uni-Cast II kV switch HVLCCA20405 DGR HVLCCB14405 DGL HVLCCB14405 DGR HVLCCB20405 DGL HVLCCB20405 DGR 15 kV switch voltsHVLCCA14415 DGL or HVLCCA20415 DGL HVLCCA20415 DGR HVLCCB14415 DGL HVLCCB14415 DGR HVLCCB20415 DGL HVLCCB20415 DGR HVL415 DEGR110-100E HVL415 DEGR2125-200E HVL415 DEGL110-100E HVL415 DEGL2125-200E HVL415 DEWR1H10-100E HVL415 DEWR2H125-200E HVL415 DEWL1H10-100E HVL415 DEWL2H125-200E Duplex switch for cable connection to Power-Dry II, Power-Cast II.

7 And Uni-Cast II kV switch HVLCCA20505 DGR HVLCCB14505 DGL HVLCCB14505 DGR HVLCCB20505 DGL HVLCCB20505 DGR 15 kV switch voltsHVLCCA14515 DGL or HVLCCA20515 DGL HVLCCA20515 DGR HVLCCB14515 DGL HVLCCB14515 DGR HVLCCB20515 DGL HVLCCB20515 DGR HVL515 DEGR110-100E HVL515 DEGR2125-200E HVL515 DEGL110-100E HVL515 DEGL2125-200E HVL515 DEWR1H10-100E HVL515 DEWR2H125-200E HVL515 DEWL1H10-100E to 38 kV E-Rated DIN medium voltage fusesTechnical Data 10638 Effective April 2017 Follow us on social media to get the latest product and support information. The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide Technical information that will help the end user with design applications.

8 Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any Technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible and Bussmann are valuable trademarks of Eaton in the and other countries. You are not permitted to use the Eaton trademarks without prior written consent of Eaton BoulevardCleveland, OH Division114 Old State RoadEllisville, MO 63021 United 2017 EatonAll Rights ReservedPrinted in USAP ublication No. 10638 BU-MC17000 April 2017