Example: barber

Technical Data Greengate CK4A – ControlKeeper 4A

Technical DataGreengateCK4A ControlKeeper 4 AOverviewThe ControlKeeper 4A network lighting control panel is a cost-effective, specification grade lighting control system. Control up to 4 relays per panel with optional support for up to four 0-10V dimming ballast control outputs. Network up to 254 ControlKeeper panels for a state of the art lighting control Support for up to four 0-10V dimming ballast outputs Electrically held normally open as well as mechanically latched and two pole relays available Capable of controlling receptacle loads 4 single pole or 2 two pole serial relays Open or closed loop control algorithmsCatalog#Prepared byProjectDateCommentsType2 September 2015CK4A ControlKeeper 4A 1 surface mount enclosureSize10 H x 14 W x DTransformer RatingsMulti-tapped 120/277 VAC internally fused standardOptional 347 VAC internally fusedOptional 220/230 VAC 50/60 Hz internally fusedOptional 220/240 VAC 50/60 Hz internally fusedPower Use RatingsFully loaded panel 40 wattsLoad Types4-wire fluorescent loads, 0-10 VDC Isolated (40 A max per circuit leakage to line)

Technical Data Greengate CK4A – ControlKeeper 4A Overview The ControlKeeper 4A network lighting control panel is a cost-effective, …

Tags:

  Data, Technical, Greengate, Controlkeeper, Technical data greengate ck4a controlkeeper, Ck4a

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Technical Data Greengate CK4A – ControlKeeper 4A

1 Technical DataGreengateCK4A ControlKeeper 4 AOverviewThe ControlKeeper 4A network lighting control panel is a cost-effective, specification grade lighting control system. Control up to 4 relays per panel with optional support for up to four 0-10V dimming ballast control outputs. Network up to 254 ControlKeeper panels for a state of the art lighting control Support for up to four 0-10V dimming ballast outputs Electrically held normally open as well as mechanically latched and two pole relays available Capable of controlling receptacle loads 4 single pole or 2 two pole serial relays Open or closed loop control algorithmsCatalog#Prepared byProjectDateCommentsType2 September 2015CK4A ControlKeeper 4A 1 surface mount enclosureSize10 H x 14 W x DTransformer RatingsMulti-tapped 120/277 VAC internally fused standardOptional 347 VAC internally fusedOptional 220/230 VAC 50/60 Hz internally fusedOptional 220/240 VAC 50/60 Hz internally fusedPower Use RatingsFully loaded panel 40 wattsLoad Types4-wire fluorescent loads, 0-10 VDC Isolated (40 A max per circuit leakage to line)

2 Each 0-10V output supports up to 50 ballasts/drivers that draw the standard 2mA eachOperating EnvironmentTemperature: 32 F to 122 F (0 C to 50 C)Master OverrideON/AUTO/OFFP rogrammingOptional PC SoftwareStandard Relay Ratings20A, 120/277 VACN ormally openMaximum wire size: 10 AWGM echanical operations: 10 millionLatching Relay Ratings20A, 120/277 VAC15A, 347 VACM aximum wire size: 6 AWGM echanical operations: 10 millionProvides a system SCCR rating of 10,000 ATwo Pole Relay Ratings20A, 208/240/480 VACN ormally openMaximum wire size: 6 AWGM echanical operations: 10 millionStandardsUL ApprovalUL 916 Listed System Includes UL listed UL 916 standard NEMA 1 enclosure 4 relays Support for 4 three-wire or 8 two-wire low voltage inputs 4 analog inputs Digital Switch interface Time schedules with astronomic clock Prioritization and masking of switch inputs, time schedules and remotes Timed inputs Occupant warn-off and overrides RS-232 port standard RS-485 network standard Open/Closed loop daylighting Control receptacle loads with Latching Relay CardAccessories Keeper Enterprise Network Software Ethernet Interface Module Automation Interface Module CEPC (UL 924 Accessory) Greengate Digital Switch (GDS)

3 Low Voltage Switches Contact Input or Analog Photocells Occupancy SensorDimensionsEnclosureWiring DiagramLatching Relay Receptacle Control3 September 2015CK4A ControlKeeper Ceiling PlanRecessedGeneral LightingLuminairesDaylightZone 1 DaylightZone 2 DaylightZone 3 Sample Circuiting Sample Switch ControlGeneral Lighting Outboard Lamps OFFC ircuit/Zone 3 Whiteboard Shuts OFFA/V Mode Lighting Center Lamp Remains ON (Full Output)General OnOffGeneral OnWhiteboardQuiet TimeAV ModeRaiseLowerGDS-6 TSB-W-D3 GDS-2 TLB-W-EC1 Sample One-LineRS-485RS-232 Relay 3 Relay 4 Relay 2 Relay 1+24 VDCDC GNDOFFONOFFON+24 OFF+24ON+24 OFF+24 ONRS-2328 low voltage inputs(Momentary, Maintained, Alternate Action switches, occupancy sensors and Photocells)Each input is software programmable to control any relay or group of switch stations can be connected to each RS-485 NetworkConnect up to 254 ControlKeeper lighting control panels and accessories1.

4 Daisy-chain all ControlKeeper lighting control panels using twisted pair (Belden #9841) or category 5 Lighting control network up to 4000 feet total length. If greater length is needed RS-485 repeaters are relay informationQty 4 - 20 amp 120/277 VAC single pole relaysAvailable normally open Individual status LED manual overrides10 AWG maximum wire size10 million operationsTypical relay wiring:LineLoad ALineLoad BLineLoad CLineLoad DThe Ethernet Interface Module (EIM) and Wireless Ethernet Interface Module (WEIM)may be connected to any lighting control panel in the system using the RS-232 cable included 120 VAC wall transformer includedEnd user computerscan program any lighting controlpanel via the Wireless Ethernet Interface Module (WEIM) using the Keeper Enterprise Occupancy Sensorfor On/Off controlIndoor Photocell:PC-I (indoor photocell)Up to four photocells connect to ControlKeeper 4A lighting control panel to adjust the lighting levelCeiling Work box by installing contractorLighting control panel power supply.

5 120/277 VAC double tap transformer standard 120/347 VAC double tap transformer is available for CanadaDimming Ballast ControlQty 4: 0-10 VDC outputsEaton1000 Eaton BoulevardCleveland, OH 44122 United systems203 Cooper CirclePeachtree City, GA 2015 EatonAll Rights ReservedPrinted in USAP ublication No. TD503047 ENSeptember 4, 2015 Eaton is a registered other trademarks are property of their respective 2015CK4A ControlKeeper 4A OrderingThis is a network-ready lighting control system. It can be combined with other ControlKeeper series panels to create a scalable, networked lighting control scheme. It can be ordered with any suitable system option or - SLRC - ck4a = ControlKeeper 4 AProductSSRCNO, SLRC, STPRCNOType of Relay CardBlank = 120/277 VAC (60 Hz) 347 = 120/347 VAC (60 Hz) 230 = 220/230 VAC (50/60 Hz) 347 = 220/240 VAC (50/60 Hz)Transformer Voltag