Transcription of Technical Data TK16 & TK32 - TracKeeper - Electrical Sector
1 Technical Data Effective October 21, 2014. tk16 & tk32 - TracKeeper Catalog# Prepared by Overview Project Date Comments Type The TracKeeper current limiting panel for track lighting allows designers to easily meet energy codes. Limiting the branch circuit volt-ampere rating with the TracKeeper provides you with a fixed power consumption limit for your installation, as opposed to calculated values based on watts per linear foot of track. Designers can now specify as many linear feet of track as desired without paying a penalty. Additionally, the use of high efficiency luminaires will often yield a lower watts/linear foot number than is specified in the code. Keep your track lighting installation options open with the TracKeeper . Features Track light current limiting panel Helps your design meet energy codes Allows track lighting installations to be based on volt-ampere rating of load instead of track length Available in 16 or 32 circuit panels Circuit breaker sizes range from to 60A.
2 Surface or flush mount options Factory assembled and ready to install Technical Data tk16 & tk32 - TracKeeper . October 2014 .. Specifications System Includes NEMA 1 enclosure Enclosure NEMA 1, 14 gauge steel, hinged locking door Hinged locking door Surface or flush mount Surface Size 16 circuit: 10 H X 14 W X 3 3/8 D As many as 16 or 32 circuit breakers 32 circuit: 16 H X 14 W X 3 3/8 D. Flush Size 16 circuit: 11 1/2 H X 15 1/2 W X 3 3/8 D. 32 circuit: 17 1/2 H X 15 1/2 W X 3 3/8 D. AIC Rating 10,000A, 120 VAC; 6,000A, 277 VAC. Available , 1, 2, 3, 4, 5, 6, 7, 8, 10, 13, 15, 16, 20, 25, 30, Circuit Breaker 32, 40, 50, 60. Ratings (A): Circuit Breaker 14 to 6 AWG. Wire Size Range Operating Temperature: 23 to 140 F (-5 C to 60 C. Environment Relative Humidity: 0 - 95%, non-condensing Standards UL 508A Listed with UL 1077 Listed circuit breakers 2 tk16 & tk32 - TracKeeper Technical Data.)
3 October 2014.. TracKeeper . Track Light Current Limiting Panel Specification Sheet Project: Prepared by: Date: Catalog #: Comments: Step 1 - Selected panel operating voltage: (120V or 277V). Step 2 - Select enclosure mounting option: (Surface or Flush Mount). Step 3 - Select panel circuit size: ( tk16 or tk32 ). Step 4 - Specify number of installed circuit breakers: (1). Step 5 - Specify each circuit breaker rating: Circuit Breaker 1 Rating (A) Circuit Breaker 17 Rating (A). Circuit Breaker 2 Rating (A) Circuit Breaker 18 Rating (A). Circuit Breaker 3 Rating (A) Circuit Breaker 19 Rating (A). Circuit Breaker 4 Rating (A) Circuit Breaker 20 Rating (A). Circuit Breaker 5 Rating (A) Circuit Breaker 21 Rating (A). Circuit Breaker 6 Rating (A) Circuit Breaker 22 Rating (A). Circuit Breaker 7 Rating (A) Circuit Breaker 23 Rating (A). Circuit Breaker 8 Rating (A) Circuit Breaker 24 Rating (A).
4 Circuit Breaker 9 Rating (A) Circuit Breaker 25 Rating (A). Circuit Breaker 10 Rating (A) Circuit Breaker 26 Rating (A). Circuit Breaker 11 Rating (A) Circuit Breaker 27 Rating (A). Circuit Breaker 12 Rating (A) Circuit Breaker 28 Rating (A). Circuit Breaker 13 Rating (A) Circuit Breaker 29 Rating (A). Circuit Breaker 14 Rating (A) Circuit Breaker 30 Rating (A). Circuit Breaker 15 Rating (A) Circuit Breaker 31 Rating (A). Circuit Breaker 16 Rating (A) Circuit Breaker 32 Rating (A). Provide Panel schedule indicating circuit breaker ratings for each location. Visit for the form. Once completed print and fax your completed form with your purchase order to 800-954-7016, or email a PDF to 3. Technical Data tk16 & tk32 - TracKeeper . October 2014 .. Ordering Specify enclosure size, mounting option, voltage and number of circuit breakers desired. tk16 - 120 - 5 - F. Product Mounting Option tk16 = 16 Size S = Surface tk32 = 32 Size F = Flush Voltage # of Breakers 120 VAC, 277 VAC 0-16 Cards = 16 Size 0-32 Cards = 32 Size Example: tk16 -120-14-F specifies a 16 circuit flush mount enclosure with 15 120V circuit breakers.
5 Eaton 1000 Eaton Boulevard Cleveland, OH 44122. United States Eaton's Cooper Controls Business 203 Cooper Circle Peachtree City, GA 30269. 2014 Eaton All Rights Reserved Eaton is a registered trademark. Printed in USA. Publication No. ACC140090 All other trademarks are property October 21, 2014 of their respective owners.