iiar 2005213 AbstractSizing ammonia Relief vents, once a simple process, has become more complicated as safety codeshave evolved. In recent years, code officials have been scrutinizing vent pipe sizing much moreheavily. The latest release of the ASHRAE Safety Standard for Refrigeration Systems devotesconsiderable ink to the sizing of Relief vents, and provides the user with an equation for determiningpressure drop in Relief Piping . This Paper will show how to use the ASHRAE equation to solve for thepressure drop in Relief vent Piping , how to select a Relief valve and three-way valve, and also showsome strategies to bring existing nonconforming installations into compliance with the iiar Ammonia Refrigeration Conference & Exhibition, Acapulco, MexicoTechnical Paper #6 Relief Vent Piping per ASHRAE 15-2004 Don Faust and Brian PetersonGartner Refrigeration & Manufacturing, , MinnesotaACKNOWLEDGEMENTThe success of the Technical program of the 27th Annual Meeting of theInternational Institute of Ammonia Refrigeration is due to the quality of the technica

C = minimum required discharge capacity of the relief valve, lbs. air/min [kg/s] f = constant, based upon the refrigerant. For ammonia, f = 0.5 [f = 0.041] D = diameter of the vessel, ft [m] L = length of the vessel, ft [m] 2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico

Tags:

  Minimum, Iiar

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Technical Paper #6 Relief Vent Piping per ASHRAE 15 ... - IIAR

1 iiar 2005213 AbstractSizing ammonia Relief vents, once a simple process, has become more complicated as safety codeshave evolved. In recent years, code officials have been scrutinizing vent pipe sizing much moreheavily. The latest release of the ASHRAE Safety Standard for Refrigeration Systems devotesconsiderable ink to the sizing of Relief vents, and provides the user with an equation for determiningpressure drop in Relief Piping . This Paper will show how to use the ASHRAE equation to solve for thepressure drop in Relief vent Piping , how to select a Relief valve and three-way valve, and also showsome strategies to bring existing nonconforming installations into compliance with the iiar Ammonia Refrigeration Conference & Exhibition, Acapulco, MexicoTechnical Paper #6 Relief Vent Piping per ASHRAE 15-2004 Don Faust and Brian PetersonGartner Refrigeration & Manufacturing, , MinnesotaACKNOWLEDGEMENTThe success of the Technical program of the 27th Annual Meeting of theInternational Institute of Ammonia Refrigeration is due to the quality of the technicalpapers in this volume.

2 iiar expresses its deep appreciation to the authors,reviewers, and editors for their contributions to the ammonia refrigeration industry. Board of Directors, International Institute of Ammonia Refrigeration ABOUT THIS VOLUMEIIAR Technical Papers are subjected to rigorous Technical peer views expressed in the papers in this volume are those of the authors, not theInternational Institute of Ammonia Refrigeration. They are not official positions ofthe Institute and are not officially endorsed. EDITORSM. Kent Anderson, PresidentChris Combs, Project CoordinatorGene Troy, , Technical DirectorInternational Institute of Ammonia Refrigeration1110 North Glebe RoadSuite 250 Arlington, VA 22201+ 1-703-312-4200 (voice)+ 1-703-312-0065 (fax) Ammonia Refrigeration Conference & ExhibitionFairmont Acapulco PrincessAcapulco, MexicoTechnical Paper #6 iiar 2005215 IntroductionBack in the old days, sizing ammonia Relief vents was a simple process.

3 Designerswould calculate the outlet area of each Relief valve in the system and make sure thatthe Relief header had at least that much area, and that was the end of it. Nocomplicated equations, no computerized solutions. However, the codes have evolved,and much more scrutiny has been given to the sizing of Relief vents in recent latest release of ASHRAE Safety Standard for Refrigeration Systems, ASHRAE 15,devotes considerable ink to the sizing of Relief vents, and provides the user with anequation for determining pressure drop in Relief Piping . ( ASHRAE , 2004) This papershows how to use the ASHRAE equation to solve for the pressure drop in Relief ventpiping, how to select a Relief valve and three-way valve, and some strategies to bringexisting nonconforming installations into compliance with the are three steps to sizing a Relief vent system:1.

4 Determine the required capacity of Relief valve for each piece of equipment2. Select Relief valves and three-way valves and determine the actual capacity of thevalves selected3. Size the Relief vent Piping systemIn this Paper , steps 2 and 3 above are assisted by a design tool, SRVQ uick, which isfreeware, a beta version of which is available through the iiar 1: Determine Required CapacityThroughout this Paper , three different Relief valve capacities will be discussed. Forclarity, they are defined as follows: Required Capacity: the calculated amount needed to protect the device. Rated Capacity: the capacity of the Relief valve with no restrictions ( , thecapacity of the valve as read directly from the manufacturer s charts).

5 Relief Vent Piping per ASHRAE 15-2004 Don Faust and Brian Peterson216 iiar 2005 Technical Paper #6 Adjusted Capacity: the capacity of the Relief valve after accounting for are Relief valves required? ASHRAE 15 states that an approved pressure Relief device must protect the followingdevices: All pressure vessels subject to the ASME Boiler and Pressure Vessel Code (vesselsless than 6 [152 mm] in diameter may use a fusible plug) Shell and tube evaporators Shell and tube condensers Positive displacement compressors (if equipped with a stop valve on thedischarge) Certain evaporators, if located near a heating coilLocal codes also may require Relief valves on other pieces of equipment ( ,evaporative condensers). Pressure Vessels and Heat ExchangersThe required Relief capacity is calculated according to the formula:C=fDL(1)where:C= minimum required discharge capacity of the Relief valve, lbs.

6 Air/min [kg/s] f=constant, based upon the refrigerant. For ammonia, f= [f= ] D=diameter of the vessel, ft [m] L= length of the vessel, ft [m]2005 iiar Ammonia Refrigeration Conference & Exhibition, Acapulco, MexicoTechnical Paper #6 iiar 2005217As a reference to the designer, Table 1 contains values of ffor several , ASHRAE 15 specifies that when combustible materials are used within20 feet [ m] of a pressure vessel, then the value of fmust be multiplied by has lead to some concern because engine rooms are often used to storerefrigerants, refrigerant oils, and even flammable fuels. OSHA makes a distinctionbetween flammableand combustible. Most refrigerants, oils and even fuels are notclassified as combustible, and thus the factor does not apply.

7 Refer to OSHA sregulations for a complete description and classification of combustible andflammable materials. (OSHA, 1996) It is interesting to note that if a receiver werelocated above a tar roof, then the factor would apply. Wood and Paper would beconsidered to be combustible solids as well. Example Vessel CalculationFind the required Relief capacity for a 42 [ m] diameter, ASME vessel, 12 ft [ m] in length, containing ammonia 1 applies in this situation:C= f D LC= ( ) ( ) (12) [C= ( ) ( ) ( )]C= 21 lbs. air/min [ kg/s]Note: To convert lbs. air/min [kg/s] to standard cubic feet per minute (SCFM) [l/s],multiply by ft3/lb [816 l/kg] (assuming dry air at 60 F [16 C]). Thus, for theabove example:C= (21) ( )[C= ( ) (816)]C= SCFM[C= 130 l/s] Relief Vent Piping per ASHRAE 15-2004 Don Faust and Brian Peterson218 iiar 2005 Technical Paper #6 Positive Displacement CompressorsSection 3 of ASHRAE 15 defines a positive displacement compressor as one inwhich the increase in pressure is attained by changing the internal volume of thecompression chamber.

8 Screw compressors and reciprocating compressors both fallinto this category. When such a compressor is equipped with a stop valve on thedischarge line, as most industrial refrigeration compressors are, a Relief device mustprotect of ASHRAE 15 separately addresses compressors that meet, and thosethat do not meet, all of the following criteria: Must be equipped with capacity regulation Can regulate capacity to minimum flow at discharge pressures equal to 90% ofthe pressure Relief setting Must be equipped with a pressure-limiting device installed and set per Section the compressor cannot regulate flow per the standard, then the Relief valve mustbe sized for the full flow of the compressor. If the compressor does meet the criteria,then the required capacity is the minimum flow of the compressor.

9 In either case,the compressor flow is calculated based upon the following conditions: High Stage: Flow is based upon 50 F [10 C] saturated suction at the compressor Booster: Flow is based upon saturated suction equal to the design operatingintermediate swing compressors, which can operate either as a booster or a high stagecompressor, the Relief valve should be sized for the worst case. This would typicallybe the high stage F of ASHRAE 15 shows an approved method of calculating the dischargecapacity of a positive displacement compressor, and the reader is referred to thatdocument for calculations from scratch. The authors requested data from all2005 iiar Ammonia Refrigeration Conference & Exhibition, Acapulco, MexicoTechnical Paper #6 iiar 2005219compressor manufacturers showing the required Relief capacity from each of theirmodels of compressors.

10 Data from the manufacturers who responded are shown inTables 2a through 2: Selecting Relief Valves and Determining their CapacityA look-up table is provided that lists the commonly used Relief valves and theirratings in lbs. air/min [kg/s]. (Table 3) Selecting a Relief valve could be as simple asfinding one in the table with at least as much capacity as is required. However, thedesigner and owner should be aware that inlet and outlet restrictions could have asignificant effect on the actual capacity of the Relief device. There are certaincombinations of Relief valves and three-way valves that can reduce the rated capacityof the Relief valve by as much as 40%. Calculating Inlet RestrictionsThe capacity of any Relief valve is reduced by the losses in the Piping and valvesbetween the Relief device and the equipment it protects.