Transcription of Thermostatic Wiring Principles - epatest.com
1 Thermostatic Wiring Principles by Bob Scaringe , Basic Thermostat Types Many technicians have great difficulty understanding how to properly wire a thermostat or how to replace a thermostat with a different thermostat. In fact, the Wiring of a thermostat is quite simple circuitry, the confusion arises principally because of the various different ways different equipment manufactures handle the heating mode of the systems and the different ways a cooling system can be interfaced with the assorted types of heating systems, ranging from furnaces, heat pumps, and electric heat or combinations of many of these heating systems operating in sequence.
2 As a start, I think the first step is to understand the basic Wiring for a simple cooling circuit of an air conditioner. Then we can add in the various methods of activating the different heating systems. First, the technician must understand, that just like a light switch circuit, to activate a relay, power is supplied from a power source to a load. In the case of HVAC/R systems, the power source is a low-voltage transformer (usually a 24 VAC transformer) and the two wires supplying the power are labeled C (common) and R.
3 The common or C wire need not be run out to the thermostat, however if the thermostat requires power, the C wire should be routed to the thermostat. Even if the current thermostat being used does not require external power it is an excellent idea to bring the C wire out to the thermostat in anticipation of a future installation of a thermostat that requires power. For systems that do not have access to the C wire, a battery in the thermostat compartment must be used.
4 This is a poor substitute for a line source of power, since the thermostat will cease to function when the battery dies. Now for the HVAC/R labeling conventions of other thermostat wires: The G wire completes the circuit from the R-leg of the power supply, back to the blower contactor coil. The coil then gets the 24 VAC from the common and G wires. Individual circuit for blower relay coil Auto All Rights Reserved, 2011, Mainstream Engineering Corporation, Rockledge, FL 2 The Y wire completes the circuit from the R-leg of the power supply back to the Compressor/Condenser fan contactor coil.
5 Individual circuit for compressor relay coil All Rights Reserved, 2011, Mainstream Engineering Corporation, Rockledge, FL 3 The W wire, if used, completes the circuit from the R-leg of the power supply back to the heater contactor coil. Sometimes there is a W1, W2, etcetera, for several stages of heating. Individual circuit for heat relay coil All Rights Reserved, 2011, Mainstream Engineering Corporation, Rockledge, FL 4 The O terminal, if used, and when the heat pump thermostat mode selector switch is set to cool, completes the circuit from the R-leg of the power supply back to the O wire.
6 It is typically used to bring power to the reversing valve and is used for a heat pump with a reversing valve where the normal (un-powered) position is for heating. If you re using the O terminal you will NOT use the B terminal. Type H reversing valve (notice O is a circuit while B is not wired) All Rights Reserved, 2011, Mainstream Engineering Corporation, Rockledge, FL 5 The B wire, if used, is closed when the heat pump thermostat mode selector switch is set to heat.
7 It is typically used to bring power back to the reversing valve and is used for a heat pump with a reversing valve where the normal (un-powered) position is for cooling. If you re using the B terminal you will NOT use the O terminal. Type C reversing valve (notice B is a circuit while O is not wired) All Rights Reserved, 2011, Mainstream Engineering Corporation, Rockledge, FL 6 The low-voltage 24 VAC transformer is typically located on the air condition system air handler. This transformer might also be located in the condensing unit, or anywhere else for that matter.
8 Locating that transformer and identifying the C (common) and R wires is likely the first thing you need to do before you begin Wiring your thermostat. Sometimes there are two low voltage transformers, one for the heating system and one for the cooling systems and the outputs of each transformer should not be connected. Having two transformers is very common if the heating system is a furnace while the cooling system is an A/C. When there is a transformer in the cooling system and a second transformer on the heating system then the R wires from each transformer must be kept separated and so they are labeled as Rc (for the R wire from cooling transformer) and Rh (for the R wire from heating transformer).
9 As we mentioned above, whenever there is an R wire there will be a C wire. So if you have two R wires you will also have two C wires. Once again, even if the thermostat you re working with runs on a battery, it s still wise to have the C wire run out to the thermostat in case the equipment owner changes the thermostat out, however only a single common or C wire needs to be run to the thermostat, and it is usually the Cc wire, that is the common wire from the cooling transformer.
10 The Rh and Ch should only be used to power relays or other components of the heating system, and the thermostat will typically only connect Rh to W (when the thermostat is calling for heating). Likewise, Rc is connected to G, Y, O, B when appropriate. This next part may be confusing at first but is If there is only one transformer, then wires labeled Rh and Rc are the same and are typically connected or jumpered together in the thermostat. Other times there is another transformer at a heating source so Rh and Rc will be different.