Example: barber

TR150 and TR170 Programming Guide - …

02/2017130R0536 MG18H202*MG18H202*February 2017 BAS-SVP16B-ENBAS-SVP16B-ENTrane has a policy of continous product and product data improvement and reserves the right tochange design and specifications without more information, contact your local Traneoffice or e-mail us at Order Number BAS-SVP16B-ENDate February 2017 Supersedes September 2013 TR150 and TR170 Programming GuideContents1 Purpose of the Document and Software Safety Safety Additional Electrical Overview72 Local Control Panel (LCP) Status Quick Main Quick Transfer of Parameter Settings between Multiple Frequency Readout and Programming of Indexed Initialization to Default Settings243 Main Menu - Operation and Display - Group Main Menu - Load and Motor - Group Main Menu - Brakes - Group Main Menu Reference/Ramps Group Main Menu - Limits/Warnings - Group Main Menu - Digital In/Out - Group Main Menu - Analog In/Out - Group Main Menu - Communications and Options - Group Main Menu - Smart Logic - Group Main Menu - Special Functions - Group Main Menu - Drive Information - Group Main Menu - Data Readouts - Group Main Menu - Data Readouts 2 - Group Main Menu - FC Closed Loop - Group Main Menu - Application Functions - Group Main Menu - Application Fu

130R0536MG18H20202/2017 *MG18H202* February 2017 BAS-SVP16B-EN BAS-SVP16B-EN Trane has a policy of continous product and product data improvement and reserves the right to

Tags:

  Policy

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of TR150 and TR170 Programming Guide - …

1 02/2017130R0536 MG18H202*MG18H202*February 2017 BAS-SVP16B-ENBAS-SVP16B-ENTrane has a policy of continous product and product data improvement and reserves the right tochange design and specifications without more information, contact your local Traneoffice or e-mail us at Order Number BAS-SVP16B-ENDate February 2017 Supersedes September 2013 TR150 and TR170 Programming GuideContents1 Purpose of the Document and Software Safety Safety Additional Electrical Overview72 Local Control Panel (LCP) Status Quick Main Quick Transfer of Parameter Settings between Multiple Frequency Readout and Programming of Indexed Initialization to Default Settings243 Main Menu - Operation and Display - Group Main Menu - Load and Motor - Group Main Menu - Brakes - Group Main Menu Reference/Ramps Group Main Menu - Limits/Warnings - Group Main Menu - Digital In/Out - Group Main Menu - Analog In/Out - Group Main Menu - Communications and Options - Group Main Menu - Smart Logic - Group Main Menu - Special Functions - Group Main Menu - Drive Information - Group Main Menu - Data Readouts - Group Main Menu - Data Readouts 2 - Group Main Menu - FC Closed Loop - Group Main Menu - Application Functions - Group Main Menu - Application Functions 2 - Group Main Menu - Special Features - Group 30954 Troubleshooting96 ContentsProgramming GuideBAS-SVP16B-EN02/2017 All rights Introduction to

2 Alarms and Alarm Warning Extended Status List of Warnings and List of LCP Errors1025 Parameter Parameter Default 0-** 1-** Load and 2-** 3-** 4-** 5-** Digital 6-** Analog 8-** Comm. and 13-** Smart 14-** Special 15-** Drive 16-** Data 18-** Info & 20-** Drive Closed 22-** Appl. 24-** Appl. Functions 30-** Special Features115 Index116 ContentsTR150 and TR170202/2017 All rights Purpose of the ManualThis Programming Guide provides information foradvanced Programming of the frequency converter. Itprovides a complete overview of all parameters anddescriptions for all Programming Guide is intended for use by operate the frequency converter safely and profes-sionally, read and follow the Programming Guide , and payparticular attention to the safety instructions and Document and Software VersionThis manual is regularly reviewed and updated. Allsuggestions for improvement are versionBAS-SVP16B-ENUpdate to newsoftware version andaddition of b l e 1.

3 1 D o c u m e nt an d S o f t wa re Ve r s i o Safety SymbolsThe following symbols are used in this Guide :WARNINGI ndicates a potentially hazardous situation that couldresult in death or serious a potentially hazardous situation that couldresult in minor or moderate injury. It can also be used toalert against unsafe important information, including situations thatcan result in damage to equipment or Safety PrecautionsWARNINGHIGH VOLTAGEF requency converters contain high voltage whenconnected to AC mains input, DC supply, or load to perform installation, start-up, and maintenanceby qualified personnel can result in death or seriousinjury. Only qualified personnel must perform instal-lation, start-up, and STARTWhen the frequency converter is connected to AC mains,DC supply, or load sharing, the motor can start at anytime. Unintended start during Programming , service, orrepair work can result in death, serious injury, orproperty damage.

4 The motor can start with an externalswitch, a fieldbus command, an input reference signalfrom the LCP or LOP, via remote operation using TraneDrive Utility (TDU), or after a cleared fault prevent unintended motor start: Press [Off/Reset] on the LCP beforeprogramming parameters. Disconnect the frequency converter from themains. Completely wire and assemble the frequencyconverter, motor, and any driven equipmentbefore connecting the frequency converter toAC mains, DC supply, or load GuideBAS-SVP16B-EN02/2017 All rights TIMEThe frequency converter contains DC-link capacitors,which can remain charged even when the frequencyconverter is not powered. High voltage can be presenteven when the warning LED indicator lights are to wait the specified time after power has beenremoved before performing service or repair work canresult in death or serious injury. Stop the motor.

5 Disconnect AC mains and remote DC-link powersupplies, including battery back-ups, UPS, andDC-link connections to other frequencyconverters. Disconnect or lock PM motor. Wait for the capacitors to discharge fully. Theminimum duration of waiting time is specifiedin Ta b l e 1 . 2. Before performing any service or repair work,use an appropriate voltage measuring device tomake sure that the capacitors are [V]Power range [kW (hp)]Minimum waiting time(minutes) ( 5) 11 (7 15) ( 10)43x40011 90 (15 125) (3 10)43x60011 90 (15 125)15Ta b l e 1 . 2 D i s c h ar g e Ti m eWARNINGLEAKAGE CURRENT HAZARDL eakage currents exceed mA. Failure to ground thefrequency converter properly can result in death orserious injury. Ensure the correct grounding of the equipmentby a certified electrical HAZARDC ontact with rotating shafts and electrical equipmentcan result in death or serious injury. Ensure that only trained and qualified personnelperform installation, start-up, and maintenance.

6 Ensure that electrical work conforms to nationaland local electrical codes. Follow the procedures in this FAILURE HAZARDAn internal failure in the frequency converter can resultin serious injury when the frequency converter is notproperly closed. Ensure that all safety covers are in place andsecurely fastened before applying Additional Resources TR150 and TR170 Quick Guide provides basicinformation on mechanical dimensions, instal-lation, and Programming TR150 and TR170 Design Guide providesinformation on how to design motor controlsystems. The Trane Drive Energy Analysis Program isavailable at software allows energy consumptioncomparisons of HVAC fans and pumps driven byTrane frequency converters and alternativemethods of flow control. Use this tool to projectthe costs, savings, and payback of using Tranefrequency converters on HVAC fans, pumps, andcooling technical literature is available in electronic form onthe documentation CD that is shipped with the product, orin print from your local Trane sales is also available online at: Drive Utility (TDU) supportDownload the software from the installation process of the software, enter CDkey 52314600.

7 A license key is not required for basicoperation. For advanced features enter license latest software does not always contain the latestupdates for frequency converters. Contact the local salesoffice for the latest frequency converter updates (in theform of *.upd files), or download the frequency converterupdates from and TR170402/2017 All rights DefinitionsFrequency converterIDRIVE, MAXThe maximum output , NThe rated output current supplied by the , MAXThe maximum output connected motor can start and stop via LCP anddigital inputs. Functions are divided into 2 groups, asdescribed in Ta b l e 1 . 3. Functions in group 1 have higherpriority than functions in group 1 Reset, coast stop, reset and coast stop, quickstop, DC brake, stop, and [Off].Group 2 Start, pulse start, reversing, start reversing, jog,and freeze Control CommandsMotorfJOGThe motor frequency when the jog function is activated(via digital terminals).

8 FMThe motor maximum motor minimum motor ,NThe rated motor frequency (nameplate data).IMThe motor ,NThe rated motor current (nameplate data).nM,NThe nominal motor speed (nameplate data).PM,NThe rated motor power (nameplate data).UMThe instantaneous motor ,NThe rated motor voltage (nameplate data).Break-away torqueIllustration Break-away Torque DRIVEThe efficiency of the frequency converter is defined as theratio between the power output and the power commandA stop command belonging to the group 1 controlcommands, see Ta b l e 1 . commandSee Ta b l e 1 . referenceA signal transmitted to the analog inputs 53 or 54. It canbe voltage or current. Current input: 0 20 mA and 4 20 mA Voltage input: 0 10 V DCBus referenceA signal transmitted to the serial communication port(drive port).Preset referenceA defined preset reference to be set from -100% to +100%of the reference range. Selection of 8 preset references viathe digital the relationship between the reference input at100% full scale value (typically 10 V, 20 mA) and theresulting reference.

9 The maximum reference value set in parameter 3-03 Maximum the relationship between the reference input at0% value (typically 0 V, 0 mA, 4 mA) and the resultingreference. The minimum reference value is set inparameter 3-02 Minimum GuideBAS-SVP16B-EN02/2017 All rights inputsThe analog inputs are used for controlling variousfunctions of the frequency are 2 types of analog inputs: Current input: 0 20 mA and 4 20 mA Voltage input: 0 10 V DCAnalog outputsThe analog outputs can supply a signal of 0 20 mA, 4 20 mA, or a digital motor adaptation, AMAThe AMA algorithm determines the electrical parametersfor the connected motor at standstill and compensates forthe resistance based on the length of the motor inputsThe digital inputs can be used for controlling variousfunctions of the frequency outputsThe frequency converter provides 2 solid-state outputs thatcan supply a 24 V DC (maximum 40 mA) outputsThe frequency converter provides 2 programmable thermal relay is a thermal load calculation basedon present load and time.

10 Its purpose is to estimate themotor temperature and prevent overheating of the initializing is carried out (parameter 14-22 OperationMode), the programmable parameters of the frequencyconverter return to their default 14-22 Operation Mode does not initializecommunication parameters, fault log, or fire mode duty cycleAn intermittent duty rating refers to a sequence of dutycycles. Each cycle consists of an on-load and an off-loadperiod. The operation can be either periodic duty or none-periodic keypad makes up a complete interface for control andprogramming of the frequency converter. The keypad isdetachable on IP20 units and fixed on IP54 units. It can beinstalled up to 3 m ( ft) from the frequency converter,that is, in a front panel with the installation kit significant for mille circular mil, an American measuring unit forcable cross-section. 1 MCM = significant parametersChanges to on-line parameters are activated immediatelyafter the data value is changed.