TrueAlarm Analog Sensing - Johnson Controls - Fire …

FeaturesModular TrueAlarm sensor base with built-inelectronic alarm sounder: Piezoelectric sounder provides high output(90 dBA) with low current requirements (17 mA) For use with interchangeable TrueAlarm sensors;photoelectric, heat, or ionization Sounder can be powered from 24 VDC or from acompatible Notification Appliance Circuit (NAC) Sounder can be synchronized coded/temporalcoded by communications* or by the NAC Sounder can be manually activated from thecontrol panel Built-in magnetic test featureTrueAlarm Analog Sensing operation: Analog sensor information is digitallycommunicated to the control panel viaMAPNET II or IDNet , two-wirecommunications** Sensor information is processed by the controlpanel to determine sensor statusFor use with Simplex control panels model 4010,4020, 4100, 4120, and Universal TranspondersFunctional and architecturally styled enclosurefor ceiling or wall mounting.

Features Modular TrueAlarm sensor base with built-in electronic alarm sounder: • Piezoelectric sounder provides high output (90 dBA) …

Tags:

  Fire, Lamar, Ultramares

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of TrueAlarm Analog Sensing - Johnson Controls - Fire …

1 FeaturesModular TrueAlarm sensor base with built-inelectronic alarm sounder: Piezoelectric sounder provides high output(90 dBA) with low current requirements (17 mA) For use with interchangeable TrueAlarm sensors;photoelectric, heat, or ionization Sounder can be powered from 24 VDC or from acompatible Notification Appliance Circuit (NAC) Sounder can be synchronized coded/temporalcoded by communications* or by the NAC Sounder can be manually activated from thecontrol panel Built-in magnetic test featureTrueAlarm Analog Sensing operation: Analog sensor information is digitallycommunicated to the control panel viaMAPNET II or IDNet , two-wirecommunications** Sensor information is processed by the controlpanel to determine sensor statusFor use with Simplex control panels model 4010,4020, 4100, 4120, and Universal TranspondersFunctional and architecturally styled enclosurefor ceiling or wall mounting.

2 Sound louvers exit both front and side for highoutput sound Smoke sensor louver design directs air flow tochamber, enhancing smoke captureOptional accessories: Remote alarm LED indicator on single gang plate Alarm LED tracking relaySSL listing status: Sensor and sounder operation is listed & Sounder SPL operation is also listed as meetingthe requirements of clause of AS3786.* Total quantity of sounder bases available for coding on the same communicationschannel may vary with panel application and availability of NAC power. Refer tospecific control panel requirements.** TrueAlarm Analog sensors and MAPNET and IDNet communications are protectedby one or more of the following Patents: 5,155,468; 5,173,683; 5,543,777;5,400,014; 5,552,765; 5,552,763; 4,796,025; DES. 377, Photoelectric Sensor Mounted inSounder Base 4098-9794 TrueAlarm Analog Sensing DescriptionSounder bases combine an audible notification applianceand a TrueAlarm Analog sensor to provide:Digital Communication of Analog provide an Analog measurement that is digitallycommunicated to the control panel where it is analyzedand an average value is determined and stored.

3 An alarmor other abnormal condition is determined by comparingthe sensor s present value against its average Data Evaluation. Monitoring each sensor saverage value provides a software filtering averagingprocess that compensates for environmental factors (dust,dirt, etc.) and component aging, providing an accuratereference for evaluating new activity. The result is asignificant reduction in the probability of false ornuisance alarms caused by shifts in sensitivity, either upor Panel Selection. Peak activity per sensor isstored to assist in evaluating specific locations. The alarmset point for each TrueAlarm sensor is determined at thecontrol panel, selectable as more or less sensitive as theindividual application Selection. Alarm set points can beprogrammed for timed automatic sensitivity selection(such as more sensitive at night, less sensitive duringday).

4 Control panel programming can also providemulti-stage operation per sensor. For example, a may cause a warning to prompt investigation while level may initiate an Alarm and Trouble LED Indication. Thecontrol panel determines when individual sensors needcleaning. Dirty sensors, or other sensor trouble, willautomatically be annunciated at the control panel and thatsensor s base LED will light steadily. In an alarmcondition, the alarmed sensor s LED will light steadily.(LED operation is controlled by the panel. During asystem alarm, a sensor LED steady on to indicate atrouble may return to pulsing to conserve communicationspower.) TrueAlarm Analog SensingSSL Listed, UL Listed Sounder Base 4098-9794 for use withTrueAlarm Photoelectric, Ionization, and Heat Sensors 1999 Simplex Time Recorder Co. All rights 8/00 Additional Sounder Base FeaturesBase mounted address selection allows the addressto remain with its programmed location when the sensoris removed for service or type change.

5 Access is from thefront under the removable sensor type identification providesdefault sensitivity when substituting sensor sensor types can be easily interchanged to meetspecific location requirements. This feature also allowsintentional sensor substitution during buildingconstruction. When conditions are temporarily dusty,instead of covering the smoke sensors (causing them to bedisabled), heat sensors may be installed withoutreprogramming the control red LED indicates power-on by pulsing, oralarm or trouble when steady on. The exact status isannunciated at the fire alarm control alarm control panel operation featuresinclude: Individual sensitivity selection for each sensor Sensitivity monitoring that satisfies NFPA 72sensitivity testing requirements Peak value logging allowing accurate analysis forsensitivity selection Automatic, once per minute individual sensorcalibration check verifies sensor integrity Automatic environmental compensation Display of sensitivity directly in percent per foot Multi-stage alarm operation Ability to display and print detailed sensor informationin plain English language4098-9822, LED Annunciation Relay activates whenbase LED is on steady, indicating a local alarm or are DPDT, rated 2 A @ 30 VDC; 1/2 A @120 VAC for transient suppressed loads (requires external24 VDC coil power).

6 2098-9808, Remote red LED Alarm Indicator mounts ona single gang box to provide status indications where thesensor location may not be readily Remote LED Alarm IndicatorMounting ReferenceSimplex Time Recorder 8/001 1/8"(29 mm)Electrical box reference for 4098-9794 Sounder base(boxes are by others) see notes below.(Photoelectric sensor shown for reference)LED status indicator is visiblefrom front access hole6 7/16" (164 mm)Sound output louversextend from front to sideNote:Single gang adapter plate (RACO No. 787 or equal)is required when using 4" square box (by others)Notes:1. Review actual wire size, wire count, box type, and whether 4098-9822 relay is used before determining box Semi-flush mounting also fits single gang handy box, 2 1/8" (51 mm) deep if wiring For surface mounted boxes, use 4" square box with single gang adapter plate (RACO No.)

7 787 or equal, by others) or 4" octagonal box with 4098-9832 Adapter When 4098-9822 LED tracking relay is mounted in electrical box, use 4" square or octagonal box with 1 1/2" extension ring, size box depth according to box 4098-9822 relay:Optional 4098-9822 Relay(Mounts in base electrical box)Relay Size: 2 1/2" X 1 1/2" X 1" ( cubic inches) (64 mm X 38 mm X mm)Mounting relay in electrical box requires additionalvolume, refer to notes Adapter Plate, required for mountingto surface mounted octagonal boxSemi-flush mount only:4" octagonal, 1 1/2" min. deepSurface or semi-flush mount:4" (102 mm) square, 1 1/2" min.(38 mm) deep AccessoriesTrueAlarm Analog Sensor FeaturesSealed against rear air flow entryElectronics are EMI/RFI shieldedHeat sensors: Selectable rate compensated, fixed temperature sensingwith or without rate-of-rise operation Listed to UL Standard 521 for 60 ft ( m) spacingfor 135 F ( C) alarm, and 40 ft ( m) spacingfor 155 F (68 C) alarmSmoke sensors: Photoelectric or ionization technology Sensing 360 smoke entry for optimum response Built-in insect screens4098-9733 Heat SensorTrueAlarm heat sensors are self-restoring and provide ratecompensated, fixed temperature Sensing , selectable withor without rate-of-rise temperature Sensing .

8 Due to itssmall thermal mass, the sensor accurately and quicklymeasures the local temperature for analysis at the firealarm control temperature detection is selectable at thecontrol panel for either 15 F ( C) or 20 F ( C)per minute. Fixed temperature Sensing is independent ofrate-of-rise Sensing and programmable to operate at135 F ( C) or 155 F (68 C). In a slow developingfire, the temperature may not increase rapidly enough tooperate the rate-of-rise feature. However, an alarm will beinitiated when the temperature reaches its rated fixedtemperature heat sensors can be programmed as a utilitydevice to monitor for temperature extremes in the rangefrom 32 F to 155 F (0 C to 68 C). This feature canprovide freeze warnings or alert to HVAC systemproblems. (Refer to specific panels for availability.)2 9/16"(65 mm)6 7/16" (164 mm)4098-9733 Heat Sensor with 4098-9794 Sounder BaseWARNING: In most fires, hazardous levels of smokeand toxic gas can build up before a heat detectiondevice would initiate an alarm.

9 In cases where LifeSafety is a factor, the use of smoke detection is Photoelectric SensorTrueAlarm photoelectric sensors use a stable, pulsedinfrared LED light source and a silicon photodiodereceiver to provide consistent and accurate low powersmoke Sensing . Seven levels of sensitivity are availablefor each individual sensor, ranging from to perfoot of smoke obscuration. Sensitivity is selected andmonitored at the fire alarm control sensor head design provides 360 smoke entry foroptimum smoke response. Due to its photoelectricoperation, air velocity is not normally a factor, except forimpact on area smoke 5/16"(58 mm)6 7/16" (164 mm)4098-9714 Photoelectric Sensor with Sounder Base4098-9717 Ionization SensorTrueAlarm ionization sensors use a single radioactivesource with an outer sampling ionization chamber and aninner reference ionization chamber to provide stableoperation under fluctuations in environmental conditionssuch as temperature and humidity.

10 Smoke and invisiblecombustion gases can freely penetrate the outer both chambers ionized by a small radioactive source[Am 241 (Americium)], a very small current flows in thecircuit. The presence of particles of combustion will causea change in the voltage ratio between chambers. Thisdifference is measured by the electronics in the sensorbase and digitally transmitted back to the control panel levels of sensitivity are available for each , , and per foot of smoke 5/16"(58 mm)6 7/16" (164 mm)4098-9717 Ionization Sensor with Sounder BaseApplication ReferenceSensor locations should be determined after carefulconsideration of the physical layout and contents of thearea to be protected. Refer to NFPA 72, the National FireAlarm Code. On smooth ceilings, smoke sensor spacingof 30 ft ( m) may be used as a guide. For detailedapplication information, refer to 4098 Detectors, Sensors,and Bases Application Manual, Part Number Time Recorder 08/00 TrueAlarm Sounder Base*ModelDescriptionCompatibilityMounti ng Requirements4098-9794 Sounder Base with connectionsfor Remote LED Alarm Indicatoror Unsupervised Relay Sensors 4098-9714, -9717, & -9733 2098-9808 remote LED alarmindicator or 4098-9822 relayRefer to page 2, mounting referenceTrueAlarm Sensors (ordered separately)ModelDescriptionMounting Requirements4098-9714 Photoelectric Smoke Sensor4098-9717 Ionization Smoke Sensor4098-9733 Heat SensorRefer to page 2, mounting referenceSounder Base Accessories (ordered separately if required)