type mvaa Tripping and Auxiliary Relays Service Manual R8009D Service ManualType MVAAT ripping and Auxiliary RelaysHANDLING OF ELECTRONIC EQUIPMENTA person's normal movements can easily generate electrostatic potentials of several thousand of these voltages into semiconductor devices when handling electronic circuits can causeserious damage, which often may not be immediately apparent but the reliability of the circuit will havebeen electronic circuits of AREVA T&D products are immune to the relevant levels of electrostaticdischarge when housed in their cases. Do not expose them to the risk of damage bywithdrawing modules module incorporates the highest practicable Protection for its semiconductor devices. However, if itbecomes necessary to withdraw a module, the following precautions should be taken to preserve the highreliability and long life for which the equipment has been designed and Before removing a module, ensure that you are at the same electrostatic potential as the equipmentby touching the Handle the module by its front-plate, frame, or edges of the printed circuit touching the electronic components, printed circuit track or Do not pass the module to any person w

Service Manual Type MVAA Tripping and Auxiliary Relays HANDLING OF ELECTRONIC EQUIPMENT A person's normal movements can easily generate electrostatic potentials of several thousand volts.

Tags:

  Types, Early, Vamas, Type mvaa

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Type MVAA - My Protection Guide

1 type mvaa Tripping and Auxiliary Relays Service Manual R8009D Service ManualType MVAAT ripping and Auxiliary RelaysHANDLING OF ELECTRONIC EQUIPMENTA person's normal movements can easily generate electrostatic potentials of several thousand of these voltages into semiconductor devices when handling electronic circuits can causeserious damage, which often may not be immediately apparent but the reliability of the circuit will havebeen electronic circuits of AREVA T&D products are immune to the relevant levels of electrostaticdischarge when housed in their cases. Do not expose them to the risk of damage bywithdrawing modules module incorporates the highest practicable Protection for its semiconductor devices. However, if itbecomes necessary to withdraw a module, the following precautions should be taken to preserve the highreliability and long life for which the equipment has been designed and Before removing a module, ensure that you are at the same electrostatic potential as the equipmentby touching the Handle the module by its front-plate, frame, or edges of the printed circuit touching the electronic components, printed circuit track or Do not pass the module to any person without first ensuring that you are both at the sameelectrostatic potential.

2 Shaking hands achieves Place the module on an antistatic surface, or on a conducting surface which is at the samepotential as Store or transport the module in a conductive information on safe working procedures for all electronic equipment can be found in BS5783 andIEC you are making measurements on the internal electronic circuitry of an equipment in service, it ispreferable that you are earthed to the case with a conductive wrist straps should have a resistance to ground between 500k 10M ohms. If a wrist strap is notavailable, you should maintain regular contact with the case to prevent the build up of which may be used for making measurements should be earthed to the case T&D strongly recommends that detailed investigations on the electronic circuitry, or modification work, should be carried out in a Special Handling Area such as described inBS5783 or IEC 4 types :MVAA 11 MVAA 12 MVAA 13 MVAA 14 MVAA 15 MVAA 16 CONTENTSSAFETY with armature operated with mechanically operated with mechanically latched settings related to the latch for MVAA 13, 14 and reset flag for self reset for hand and self reset for hand reset and electrically reset units.

3 MVAA 13, 14 and 15 for reset levers on hand reset and hand/electrically reset to current taken by contacts not changing TEST RECORD17 REPAIR FORM19 Page 5 SAFETY SECTIONThis Safety Section should be read before commencing any work on the and safetyThe information in the Safety Section of the product documentation is intended toensure that products are properly installed and handled in order to maintain them ina safe condition. It is assumed that everyone who will be associated with theequipment will be familiar with the contents of the Safety of symbols and labelsThe meaning of symbols and labels which may be used on the equipment or in theproduct documentation, is given : refer to product documentationCaution: risk of electric shockProtective/safety *earth terminalFunctional *earth : this symbol may also be used for a protective/safety earth terminal if that terminal is part of aterminal block or sub-assembly eg.

4 Power supply.*Note: The term earth used throughout the product documentation is the directequivalent of the North American term , Commissioning and ServicingEquipment connectionsPersonnel undertaking installation, commissioning or servicing work on thisequipment should be aware of the correct working procedures to ensure product documentation should be consulted before installing, commissioning orservicing the exposed during installation, commissioning and maintenance may presenta hazardous voltage unless the equipment is electrically there is unlocked access to the rear of the equipment, care should be taken by allpersonnel to avoid electric shock or energy and current connections should be made using insulated crimp terminationsto ensure that terminal block insulation requirements are maintained for safety.

5 Toensure that wires are correctly terminated, the correct crimp terminal and tool for thewire size should be 6 Before energising the equipment it must be earthed using the protective earthterminal, or the appropriate termination of the supply plug in the case of plugconnected equipment. Omitting or disconnecting the equipment earth may cause asafety recommended minimum earth wire size is mm2, unless otherwise stated inthe technical data section of the product energising the equipment, the following should be checked:Voltage rating and polarity;CT circuit rating and integrity of connections;Protective fuse rating;Integrity of earth connection (where applicable)Equipment operating conditionsThe equipment should be operated within the specified electrical and transformer circuitsDo not open the secondary circuit of a live CT since the high voltage producedmay be lethal to personnel and could damage resistorsWhere external resistors are fitted to relays, these may present a risk of electric shockor burns, if replacementWhere internal batteries are fitted they should be replaced with the recommendedtype and be installed with the correct polarity, to avoid possible damage to and dielectric strength testingInsulation testing may leave capacitors charged up to a hazardous voltage.

6 At theend of each part of the test, the voltage should be gradually reduced to zero, todischarge capacitors, before the test leads are of modules and pcb cardsThese must not be inserted into or withdrawn from equipment whilst it is energised,since this may result in optic communicationWhere fibre optic communication devices are fitted, these should not be vieweddirectly. Optical power meters should be used to determine the operation or signallevel of the 7 Older ProductsElectrical adjustmentsEquipments which require direct physical adjustments to their operating mechanism tochange current or voltage settings, should have the electrical power removed beforemaking the change, to avoid any risk of electric adjustmentsThe electrical power to the relay contacts should be removed before checking anymechanical settings, to avoid any risk of electric out case relaysRemoval of the cover on equipment incorporating electromechanical operatingelements, may expose hazardous live parts such as relay and withdrawal of extender cardsWhen using an extender card, this should not be inserted or withdrawn from theequipment whilst it is energised.

7 This is to avoid possible shock or damage live voltages may be accessible on the extender and withdrawal of heavy current test plugsWhen using a heavy current test plug, CT shorting links must be in place beforeinsertion or removal, to avoid potentially lethal and DisposalDecommissioning:The auxiliary supply circuit in the relay may include capacitorsacross the supply or to earth. To avoid electric shock or energyhazards, after completely isolating the supplies to the relay(both poles of any dc supply), the capacitors should be safelydischarged via the external terminals prior to :It is recommended that incineration and disposal to watercourses is avoided. The product should be disposed of in a safemanner. Any products containing batteries should have themremoved before disposal, taking precautions to avoid shortcircuits.

8 Particular regulations within the country of operation,may apply to the disposal of lithium 8 Technical SpecificationsProtective fuse ratingThe recommended maximum rating of the external protective fuse for this equipmentis 16A, Red Spot type or equivalent, unless otherwise stated in the technical datasection of the product class:IEC 61010-1: 1990/A2: 1995 This equipment requires aClass Iprotective (safety) earthEN 61010-1: 1993/A2: 1995 connection to ensure userClass 61010-1: 1990/A2: 1995 Distribution level, fixedCategoryCategory IIIinstallation. Equipment in(Overvoltage):EN 61010-1: 1993/A2: 1995 this category is qualificationCategory IIItested at 5kV peak, s,500 , , between all supplycircuits and earth and alsobetween independent :IEC 61010-1: 1990/A2: 1995 Compliance is demonstrated byPollution degree 2reference to generic safetyEN 61010-1: 1993/A2: 1995 degree 2 Product safety:73/23/EECC ompliance with the EuropeanCommission Low 61010-1: 1993/A2: 1995 Compliance is demonstratedEN 60950:1992/A11: 1997 by reference to generic 9 Section relays, although generally of robust construction, require careful treatmentprior to installation and a wise selection of site.

9 By observing a few simple rules thepossiblity of premature failure is eliminated and a high degree of performance canbe relays are either despatched individually or as part of a panel/rack mountedassembly in cartons specifically designed to protect them from should be examined immediately they are received to ensure that no damagehas been sustained in transit. If damage due to rough handling is evident, a claimshould be made to the transport company concerned immediately, and the nearestAREVA T&D representative should be promptly which are supplied unmounted and not intended for immediate installationshould be returned to their protective polythene must be taken when unpacking and installing the relays so that none of theparts are damaged or their settings altered, and must only be handled by should be examined for any wedges, clamps, or rubber bands necessary tosecure moving parts to prevent damage during transit and these should be removedafter installation and before which have been removed from their cases should not be left in situationswhere they are exposed to dust or damp.

10 This particularly applies to installationswhich are being carried out at the same time as constructional relays are not installed immediately upon receipt they should be stored in a placefree from dust and moisture in their original cartons and where de-humidifier bagshave been included in the packing they should be retained. The action of the de-humidifier crystals will be impaired if the bag has been exposed to ambientconditions and may be restored by gently heating the bag for about an hour, prior toreplacing it in the which collects on a carton may, on subsequent unpacking, find its way into therelay; in damp conditions the carton and packing may become impregnated withmoisture and the de-humidifying agent will lose its storage temperature range is 25 C to +70 installation should be clean, dry and reasonably free from dust and excessivevibration.