Usage DisclaimerAuthorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation anduse of UL Certified products, equipment, system, devices, and Having Jurisdiction should be consulted before resistance assemblies and products are developed by the Design submitter and have been investigated by UL forcompliance with applicable requirements. The published information cannot always address every construction nuanceencountered in the field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the productmanufacturer noted for the Design . Users of fire resistance assemblies are advised to consult the general Guide Information foreach product category and each group of assemblies.

Jul 31, 2021 · Framing Member s* - Steel Studs — (As an alternate to Item 2, For use with Items 5C, 5I or Type ULIX) — Proprietary channel. shaped studs, 3-5/8 in. deep spaced a max of 24 in. OC. S tuds to be cut 3/4 in less than the assembly height and installed with a 1/2. in. gap between the end of the stud and track at the bottom of the wall.

Tags:

  Walls, Farming

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of UL Design U419 - 1, 2, 3 or 4 Hour Wall Assembly ...

1 Usage DisclaimerAuthorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation anduse of UL Certified products, equipment, system, devices, and Having Jurisdiction should be consulted before resistance assemblies and products are developed by the Design submitter and have been investigated by UL forcompliance with applicable requirements. The published information cannot always address every construction nuanceencountered in the field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the productmanufacturer noted for the Design . Users of fire resistance assemblies are advised to consult the general Guide Information foreach product category and each group of assemblies.

2 The Guide Information includes specifics concerning alternate materialsand alternate methods of products which bear UL's Mark are considered - Fire Resistance Ratings - ANSI/UL 263 Certified for United StatesBXUV7 - Fire Resistance Ratings - CAN/ULC-S101 Certified for CanadaSee General Information for Fire-resistance Ratings - ANSI/UL 263 Certified for United States Design Criteria and Allowable VariancesSee General Information for Fire Resistance Ratings - CAN/ULC-S101 Certified for Canada Design Criteria and Allowable VariancesDesign No. U419 July 31, 2021 Nonbearing Wall Ratings 1, 2, 3 or 4 Hr (See Items 4 & 5 through 5J)* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification(such as Canada), Floor and Ceiling Runners (Not Shown) For use with Item 2 Channel shaped, fabricated from min 25 MSG corrosion-protected steel, min depth to accommodate stud size, with min 1-1/4 in.

3 Long legs, attached to floor and ceiling with fasteners 24 Framing Members* Floor and Ceiling Runner Not Shown In lieu of Item 1 For use with Item 2B, proprietary channelshaped runners, 3-5/8 in. deep attached to floor and ceiling with fasteners 24 in. OC EXPANDED METAL PRODUCTS CO Viper25 TrackCRACO MFG INC SmartTrack25 MARINO/WARE, DIV OF WARE INDUSTRIES INC Viper25 TrackFUSION BUILDING PRODUCTS Viper25 TrackIMPERIAL MANUFACTURING GROUP INC Viper25 Track1B. Framing Members* Floor and Ceiling Runner Not Shown In lieu of Item 1 For use with Item 2C, proprietary channelshaped runners, 1-1/4 in. wide by 3-5/8 in. deep fabricated from min in. thick galv steel, attached to floor and ceiling withfasteners spaced 24 in.

4 OC EXPANDED METAL PRODUCTS CO Viper20 TrackMARINO/WARE, DIV OF WARE INDUSTRIES INC Viper20 TrackFUSION BUILDING PRODUCTS Viper20 TrackIMPERIAL MANUFACTURING GROUP INC Viper20 Track1C. Framing Members* Floor and Ceiling Runners (Not Shown) In lieu of Item 1 Channel shaped, attached to floor andceiling with fasteners 24 in. OC. & GYPSUM PRODUCTS INC Type SUPREME D24/30 EQD and Type SUPREME D20 CONSOLIDATED FABRICATORS CORP, BUILDING PRODUCTS DIV Type SUPREME D24/30 EQD and Type SUPREME D20 QUAIL RUN BUILDING MATERIALS INC Type SUPREME D24/30 EQD and Type SUPREME D20 SCAFCO STEEL STUD MANUFACTURING CO Type SUPREME D24/30 EQD and Type SUPREME D20 STEEL CONSTRUCTION SYSTEMS INC Type SUPREME D24/30 EQD and Type SUPREME D20 TELLING INDUSTRIES L L C Type SUPREME D24/30 EQD and Type SUPREME D20 UNITED METAL PRODUCTS INC Type SUPREME D24/30 EQD and Type SUPREME D201D.

5 Floor and Ceiling Runners (Not Shown) For use with Item 2A Channel shaped, fabricated from min 20 MSG corrosion-protected or galv steel, min depth to accommodate stud size, with min 1 in. long legs, attached to floor and ceiling with fastenersspaced max 24 in. Framing Members* Floor and Ceiling Runners (Not Shown, As an alternate to Item 1) For use with Items 2E, 5F or 5G or5I only, channel shaped, fabricated from min. in. (min bare metal thickness) galvanized steel, attached to floor and ceiling withfasteners 24 in. OC. BUILDING SYSTEMS CD ProTRAKDMFCWBS L L C ProTRAKMBA METAL FRAMING ProTRAKRAM SALES L L C Ram ProTRAKSTEEL STRUCTURAL PRODUCTS L L C Tri-S ProTRAK1F. Framing Members* Floor and Ceiling Runner Not Shown In lieu of Item 1 For use with Item 2F, proprietary channelshaped runners, minimum width to accommodate stud size, with 1- 1/8 in.

6 Long legs fabricated from min in. (min bare metalthickness) galv steel, attached to floor and ceiling with fasteners spaced 24 in. OC STUD BUILDING PRODUCTS The Edge1G. Framing Members* Floor and Ceiling Runner For use with Item 2G, proprietary channel shaped runners, minimum widthto accommodate stud size attached to floor and ceiling with fasteners 24 in. OC BUILDING SYSTEMS CROCSTUD Track1H. Floor and Ceiling Runners (Not Shown) Channel shaped, fabricated from min in. galv steel, min width toaccommodate stud size, with min 1 in. long legs, for use with studs specified below and fabricated from min in. galv steel orthicker, attached to floor and ceiling with fasteners spaced max 24 in. , DIV OF WARE INDUSTRIES INC Viper20 Track VT100 FUSION BUILDING PRODUCTS Viper20 Track VT100 IMPERIAL MANUFACTURING GROUP INC Viper20 Track VT1001I.

7 Framing Members* Floor and Ceiling Runners (Not Shown, As an alternate to Item 1) For use with Items 2H, channelshaped, fabricated from min. in. (min bare metal thickness) galvanized steel, attached to floor and ceiling with fasteners 24 INDUSTRIES L L C TRUE-TRACK 1J. Framing Members* Floor and Ceiling Runner Not Shown In lieu of Item 1 For use with Item 2I, proprietary channelshaped runners, 3-5/8 in. deep attached to floor and ceiling with fasteners 24 in. OC Framing Members* Floor and Ceiling Runner Not Shown In lieu of Item 1 For use with Item 2J, proprietary channelshaped runners, 1-1/4 in. wide by 3-5/8 in. deep fabricated from min in. thick galv steel, attached to floor and ceiling withfasteners spaced 24 in.

8 OC Framing Members* Floor and Ceiling Runner Not Shown In lieu of Item 1 For use with Item 2N, proprietary channelshaped runners, 1-1/4 in. wide by min. 3-1/2 in. deep fabricated from min in. thick galv steel, attached to floor and ceiling withfasteners spaced 24 in. OC METAL FRAMING, L L C AlphaTRAK1M. Framing Members* Floor and Ceiling Runners Not Shown As an alternate to Item 1 For use with Item 2O,proprietary channel shaped runners, min width to accommodate stud size, galv steel, attached to floor and ceiling with fastenersspaced 24 in. OC BUILDING SERVICES PTY LTD Rondo Wall Track1N. Framing Members* Floor and Ceiling Runners Not Shown As an alternate to Item 1 For use with Item 2P,proprietary channel shaped runners, min width to accommodate stud size, galv steel, attached to floor and ceiling with fastenersspaced 24 in.

9 OC BUILDING MATERIALS OEG Track1O. Framing Members* Floor and Ceiling Runner Not Shown In lieu of Item 1 For use with Item 2Q, proprietary channelshaped runners, min width to accommodate stud size, fabricated from min. 25 MSG ( in. min. bare metal thickness), attached tofloor and ceiling with fasteners spaced 24 in. OC EXPANDED METAL PRODUCTS CO Viper X Track2. Steel Studs Channel shaped, fabricated from min 25 MSG corrosion-protected steel, min depth as indicated under Item 5,spaced a max of 24 in. OC. Studs to be cut 3/8 to 3/4 in. less than Assembly Steel Studs (As an alternate to Item 2, For use with Items 5B, 5E, 5H, 5J or Type ULIX) Channel shaped, fabricated from min20 MSG corrosion-protected or galv steel, 3-1/2 in.

10 Min depth, spaced a max of 16 in. OC. Studs friction-fit into floor and ceilingrunners. Studs to be cut 5/8 to 3/4 in. less than Assembly Framing Members* - Steel Studs (As an alternate to Item 2, For use with Items 5C, 5I or Type ULIX) Proprietary channelshaped studs, 3-5/8 in. deep spaced a max of 24 in. OC. Studs to be cut 3/4 in less than the Assembly height and installed with a 1/2in. gap between the end of the stud and track at the bottom of the wall. For direct attachment of gypsum board EXPANDED METAL PRODUCTS CO Viper25 CRACO MFG INC SmartStud25 MARINO/WARE, DIV OF WARE INDUSTRIES INC Viper25 FUSION BUILDING PRODUCTS Viper25 IMPERIAL MANUFACTURING GROUP INC Viper25 2C. Framing Members* Steel Studs Not Shown In lieu of Item 2 proprietary channel shaped steel studs, min depth asindicated under Item 5, spaced a max if 24 in.