Transcription of Victaulic Flexible Coupling Style 75 Submittal
1 Victaulic Flexible Coupling Style 75 Exaggerated for clarity 1 8"/DN25 DN200 Exaggerated for clarity PRODUCT DESCRIPTION. Available Sizes 1 8"/DN25 DN200. Pipe Material Carbon steel Stainless steel Maximum Working Pressure Accommodates pressures ranging from full vacuum ( in Hg/760 mm Hg) up to 500 psi/3447 kPa/34 bar Working pressure dependent on material, wall thickness and size of pipe Application Joins standard roll grooved and cut grooved pipe, as well as grooved fittings, valves and accessories Provides a Flexible pipe joint which allows for expansion, contraction and deflection Up to 50% lighter in weight than standard Victaulic Style 77 or Style 177N Flexible couplings CERTIFICATION/LISTINGS.
2 NOTES. Download publication for Fire Protection Certifications/Listings Reference Guide. See publication : Victaulic Potable Water Approvals ANSI/NSF for potable water approvals if applicable. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. System No. Location Spec Section Paragraph Submitted By Date Approved Date 1470 Rev P Updated 10/2017 2017 Victaulic Company. All rights reserved. 1. SPECIFICATIONS MATERIAL. Housing: Ductile iron conforming to ASTM A536, Grade 65-45-12.
3 Ductile iron conforming to ASTM A395, Grade 65-45-15, is available upon special request. Housing Coating: (specify choice). Standard: Orange enamel Optional: Hot dipped galvanized Optional: Contact Victaulic with your requirements for other coatings. Gasket: (specify choice1). Grade E EPDM. EPDM (Green stripe color code). Temperature range 30 F to +230 F/ 34 C to +110 C. May be specified for hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. UL Classified in accordance with ANSI/NSF 61 for cold +73 F/+23 C and hot +180 F/+82 C.
4 Potable water service and ANSI/NSF 372. NOT COMPATIBLE FOR USE WITH PETROLEUM SERVICES OR. STEAM SERVICES. Grade T Nitrile . Nitrile (Orange stripe color code). Temperature range 20 F to +180 F/ 29 C to +82 C. May be specified for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range; not compatible for hot dry air over +140 F/+60 C and water over +150 F/+66 C. NOT COMPATIBLE FOR USE. WITH HOT WATER. Others For alternate gasket selection, reference publication : Victaulic Seal Selection Guide - Elastomeric Seal Construction.
5 1 Services listed are General Service Guidelines only. It should be noted that there are services for which these gaskets are not compatible. Reference should always be made to the latest Victaulic Seal Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts: (specify choice2). Standard: Carbon steel oval neck track bolts meeting the mechanical property requirements of ASTM A449 (imperial). and ISO 898-1 Class (metric). Carbon steel hex nuts meeting the mechanical property requirements of ASTM.
6 A563 Grade B (imperial - heavy hex nuts) and ASTM A563M Class 9 (metric - hex nuts). Track bolts and hex nuts are zinc electroplated per ASTM B633 ZN/FE5, finish Type III (imperial) or Type II (metric). Optional (imperial): Stainless steel oval neck track bolts meeting the mechanical property requirements of ASTM. F593, Group 2 (316 stainless steel), condition CW. Stainless steel heavy nuts meeting the mechanical property requirements of ASTM F594, Group 2 (316 stainless steel), condition CW, with galling reducing coating. 2 Optional bolts/nuts are available in imperial sizes only.
7 1470 Rev P Updated 10/2017 2017 Victaulic Company. All rights reserved. 2. DIMENSIONS. Style 75. Y Z. X. Pipe End Deflection from Size Separation3 Centerline3 Bolt/Nut Dimensions Weight Actual Outside Approx. Nominal Diameter Allowable Per Cplg. Pipe Qty. Size X Y Z (Each). inches inches inches inches/ft. imperial inches inches inches lb DN mm mm Degrees mm/m metric mm mm mm kg 1 0 3/8 x 2 2 43' 2. DN25 0 48 M10 x 51 61 108 45 1 1/4 0 3/8 x 2 2 10' 2. DN32 0 38 M10 x 51 68 117 45 1 1/2 0 3/8 x 2 1 56' 2. DN40 0 33 M10 x 51 74 122 45 2 0 3/8 x 2 1 31' 2.
8 DN50 0 26 M10 x 51 87 133 48 2 1/2 0 3/8 x 2 1 15' 2. 0 22 M10 x 51 98 144 48 0 3/8 x 2 1 12' 2. DN65 0 22 M10 x 51 102 150 48 3 0 1/2 x 2 3/4 1 2' 2. DN80 0 18 M12 x 70 114 178 48 3 1/2 0 1/2 x 2 3/4 0 -54' 2. DN90 0 16 M12 x 70 127 191 48 4 0 1/2 x 2 3/4 1 36' 2. DN100 0 28 M12 x 70 147 204 54 0 1/2 x 2 3/4 1 41' 2. 0 29 M12 x 70 141 198 54 0 5/8 x 3 1/4 1 26' 2. 0 21 M16 x 83 156 240 54 5 0 5/8 x 3 1/4 1 18' 2. 0 23 M16 x 83 175 256 54 0 5/8 x 3 1/4 1 21' 2. 0 24 M16 x 83 166 238 54 0 5/8 x 3 1/4 1 18' 2. DN125 0 24 M16 x 83 173 244 54 0 5/8 x 3 1/4 1 12' 2.
9 0 18 M16 x 83 187 266 48 6 0 5/8 x 3 1/4 1 5' 2. DN150 0 18 M16 x 83 203 281 54 0 5/8 x 3 1/4 1 9' 2. 0 20 M16 x 83 194 266 54 0 5/8 x 3 1/4 1 7' 2. 0 58 M16 x 83 199 271 53 0 3/4 x 4 1/4 0 51' 2. 0 46 M20 x 108 259 350 59 8 0 3/4 x 4 1/4 0 50' 2. DN200 0 14 M20 x 108 263 355 59 3 Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe. Figures for standard cut grooved pipe may be doubled. These figures are maximums; for design and installation purposes these figures should be reduced by: 50% for 3/4 3 1/2"/DN20 DN90; 25% for 4"/DN100 and larger.
10 NOTE. Metric thread size bolts are available (color coded gold) for all Coupling sizes upon request. Contact Victaulic for details. 1470 Rev P Updated 10/2017 2017 Victaulic Company. All rights reserved. 3. PERFORMANCE. Style 75. Size Actual Maximum Outside Working Maximum Nominal Diameter Pressure4 End Load4. inches inches psi lb DN mm kPa N. 1 500 680. DN25 3447 3,025. 1 1/4 500 1080. DN32 3447 4,805. 1 1/2 500 1420. DN40 3447 6,320. 2 500 2215. DN50 3447 9,860. 2 1/2 500 3245. 3447 14,440. 500 3535. DN65 3447 15,730. 3 500 4800.