Weil McLain Troubleshooting Guide

C-1013 Copyright 2006 Plus Water Heaters Service Technician s Troubleshooting GuideThis Guide is to be used in conjunction with all GOLD and ULTRA Plus30/40/60/80 and PLUS 100/110/119/120 Indirect Fired Water HeaterTechnical Specification Manuals Maintenance Trouble Shooting PracticesBefore leaving for the job site: Check your parts and Test equipment and tools that you will need:Electrical meter that can measure voltage and continuityPressure gauge, Watts #276H300 test gaugeTemperature gauge and StopwatchBucket, 1 gallon or larger with volume markingsThermostat (Aquastat) W-M P/N 633-900-130 for GOLD/Ultra Plus30/40/60/80 Thermostat (Aquastat) W-M P/N 635-100-010 for PLUS 100/110/119/120 Drywell seal repair kit W-M P/N 635-600-150 Know the water heater model number.

- Recirculation loop Boiler Relief Valve Lifting or Weeping - page 7 ... i.e. ASHRAE sizing tables, or ASPE domestic water heating design manual, re-confirm the water demand required for ... based on nozzle size and pump pressure. - Does the hot water system need to be wired for domestic priority? For systems in which

Tags:

  Pumps, Sizing, Recirculation

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Weil McLain Troubleshooting Guide

1 C-1013 Copyright 2006 Plus Water Heaters Service Technician s Troubleshooting GuideThis Guide is to be used in conjunction with all GOLD and ULTRA Plus30/40/60/80 and PLUS 100/110/119/120 Indirect Fired Water HeaterTechnical Specification Manuals Maintenance Trouble Shooting PracticesBefore leaving for the job site: Check your parts and Test equipment and tools that you will need:Electrical meter that can measure voltage and continuityPressure gauge, Watts #276H300 test gaugeTemperature gauge and StopwatchBucket, 1 gallon or larger with volume markingsThermostat (Aquastat) W-M P/N 633-900-130 for GOLD/Ultra Plus30/40/60/80 Thermostat (Aquastat) W-M P/N 635-100-010 for PLUS 100/110/119/120 Drywell seal repair kit W-M P/N 635-600-150 Know the water heater model number.

2 Know boiler manufacturer and model number. Have the Installation and Maintenance Manual and/or wiring and pipingschematic readily the latest revisions from !!Follow the Troubleshooting Guide step by step, always double checking yourresults. Skipping steps or not completing steps can lead to wrong conclusions,repeated visits to the job site, and unhappy 2006 Insufficient Hot Water - page 3- Undersized water heater- Boiler system improperly sized- Check component parts- Boiler operating temperature- Location of flow control devices- Air in system- Clean boiler systemExcessive Water Temperature - page 6- Reduce Stacking- Lowering boiler operating temperature- Relocating T-stat bulb- Reverse boiler piping- Install thermostatic mixing valve- recirculation loopBoiler Relief Valve Lifting or Weeping - page 7- Undersized boiler expansion tank- Faulty boiler expansion tank- Simulate maximum expansion.

3 Faulty boiler relief valve- Faulty boiler fill valve- Inner tank leakT&P Relief Valve Lifting or Weeping - page 8- Undersized or missing domestic side expansion tank- Faulty domestic expansion tank- Faulty T&P relief valve- High domestic supply pressure- Possible water hammering or pressure spikes- Boiler operating temperatureWater on the Floor - page 9- From sources other than the water heater- T&P valve lifting and discharging- Loose piping connectionsTop of Tank / Insulation Wet - page 10- From sources other than the water heater- Loose piping connections- Leakage from the drywellWater Smells / Taste Bad - page 11- Water smells like "rotten eggs"- Milky water- Rusty discolored waterYe sYe sYe sYe sYe sYe sYe sINSUFFICIENTHOTWATEREXCESSIVEDOMESTICWA TERTEMPERATUREBOILERRELIEFVALVELIFTINGOR WEEPINGTEMPERATURE/PRESSURERELIEFVALVELI FTINGORWEEPINGWATERFOUND ONTHEFLOORNEARTHETANKTOP OFTANK/INSULATIONWETWATERQUALITYPROBLEMS 2Is the water heater undersized for the application?

4 (Non-Warranty)- There are many methods of sizing various applications, ASHRAE sizing tables, orASPE domestic water heating design manual, re-confirm the water demand required forthe Re-confirm the flow rates of the fixtures. Was the tank sized for shower heads at gpm,when the actual heads are gpm? Use a bucket and a stopwatch to determine fixtureflow Evaluate the hot water usage pattern for a day. Is the peak demand unusually high for theapplication?- Has the demand for domestic hot water changed since the system was installed? Abathroom remodeling project with a newly installed whirlpool tub will drastically changethe domestic water the boiler system properly sized?

5 (Non-Warranty)- Is the boiler providing the required output of BTU s to meet the domestic water load?Temp Rise F = Desired Temp. F - Incoming Temp. = Density of Water lbs/gal. x 1 Btu/lbs FExample: A single family home with a gpm shower fixture and a 150,000 Btu/hr outputboiler capacity. Is the boiler capacity adequate to deliver 115 F water for an extended period?The boiler capacity is capable of delivering gpm continuously which isadequate for this Item:- Measure the BTU input to the boiler by clocking the gas meter or finding the oil flow ratebased on nozzle size and pump Does the hot water system need to be wired for domestic priority?

6 For systems in whicheither the storage or BTU s available are marginal, it is recommended to wire the domesticwater heater in a priority Is the boiler piping to the water heater properly sized to allow the required flow rate formaximum BTU transfer? The temperature differential of the boiler supply and returnwater should be 20 F to 30 Demand gph=Blr Output BTU s(Temp. Rise F x )Domestic Demand gph=150,000 Btu/hr[(115 F-50 F) x ]= 277 gph3- Is the circulator between the boiler and the water heater properly sized to provide adequateflow for maximum BTU transfer?

7 Check component parts- Is the domestic water thermostat functioning properly? With a electrical voltmeter checkfor continuity between terminals C and 1 on the snap-set Item:1. Disconnect the snap-set connector on the water Turn the thermostat knob to the highest setting - clockwise to initiate a call for Check for continuity between terminals C and 1 (end connectors on the snap-set). On acall for heat, these contacts should be in the close Continue checking for continuity while turning the thermostat knob to the lowest setting- counter clockwise to satisfy the call for heat.

8 The contacts should open, breaking If any of these steps fail (1-4 above), replace the thermostat. (Warranty)For 30/40/60/80 - P/N 633-900-130 for 100/110/119/120 - P/N Reconnect the Is the thermostat setting too low? If the thermostat setting is too low, the boiler may nothave the opportunity to deliver the maximum BTU s required to completely heat theentire volume of water stored in the During a call for heat by the water heater, does the boiler circulator begin pumping, doesthe zone valve open, does the boiler fire? Check every component in the system to ensurethey are properly Check the thermostat sensing bulb size and fit into the drywell.

9 Some older units have asensing bulb that is thinner and fits loose inside the drywell. The newer thermostats have alarger bulb which fits tighter in the drywell allowing better heat transfer for more accuratewater temperature sensing. Action Item:- If the sensing bulb does not slide into the drywell; remove burrs from top 1 1/2 inside thedrywell with a 3/8 'STRANSFER3/4"3 to 7 gpm50 to 100 MBH1"4 to 11 gpm100 to 180 MBH1 1/4"6 to 16 gpm160 to 300 MBH1 1/2"9 to 23 gpm200 to 450 MBH2"15 to 40 gpm300 to 650 MBH4- What is the location of the thermostat bulb? A bulb inserted completely at the bottom ofthe drywell will initiate a quicker response for a call for heat.

10 This is typically the positionof the bulb required for applications in which there are large draws of domestic Remove and examine the dip tube located in the cold water inlet. Replace if damaged. Abroken or melted dip tube will cause the cold water to discharge across the top of the tank,thus short cycling the water the operating temperature of the boiler (Non-Warranty)- If possible increase the boiler operating temperature to 200 Maintain a minimal temperature in the boiler during non-heating seasons. A boilertypically has a higher standby loss than the indirect water heater.