Wiring Diagrams - AutomationDirect

The HPS Imperatortm series of machine tool industrial molded control transformers are available in many standard offerings. This Wiring hook-up instruction sheet refers to all standard HPS Imperatortm series part number suffixes. (Note: standard econdary fuse kits (not installed) supplied with each transformer unless otherwise indicated; field insatlled primary fuse kits sold separately; fuses not available from HPS.)If you have any questions regarding these Wiring Diagrams or are having any difficulty correctly installing our transformers, please contact HPS customer service or technical support in the at 1-866-705-4684 or in Canada at ImperatortmIndustrial Control TransformerWiring DiagramsIssue Date: October 2007 rev4 Page 1 of 9 Literature Code: PHWD1-2 HPS Imperatortm Series - Wiring Schematic Drawings4143212 1346674 312558 HVL V1 243575V600V550V115V230V120V240V110V220V5 254323 24561116564213778L V2134HV56575V600V550V115V230V120V240V110 V220 VPH**AJ Schematic for 50, 75 and 100VA UnitsPH**AJ Schematic for 150VA to 1500VA Units High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse (Primary Volts) Links Between Terminals Connect To Clips To 600 575 550 None 1, 4 Unfused 600 575 550 None 6, 7 1-5, 4-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 120 115 110 3-4, 1-2 1, 4 Unfused 240 230 220 2-3 1, 4 Unfused 120 115 110 3-4, 1-2 4.

Page 5 of 9 HPS Imperator tm Series - Wiring Schematic Drawings continued 2 5 5 4 3 2 6 5 4 3 2 1 1 1 6 6 5 4 3 2 1 7 7 8 LV 1 2 3 4 HV 5 6 575V 600V 550V 11.5V 23V ...

Tags:

  Wiring

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Wiring Diagrams - AutomationDirect

1 The HPS Imperatortm series of machine tool industrial molded control transformers are available in many standard offerings. This Wiring hook-up instruction sheet refers to all standard HPS Imperatortm series part number suffixes. (Note: standard econdary fuse kits (not installed) supplied with each transformer unless otherwise indicated; field insatlled primary fuse kits sold separately; fuses not available from HPS.)If you have any questions regarding these Wiring Diagrams or are having any difficulty correctly installing our transformers, please contact HPS customer service or technical support in the at 1-866-705-4684 or in Canada at ImperatortmIndustrial Control TransformerWiring DiagramsIssue Date: October 2007 rev4 Page 1 of 9 Literature Code: PHWD1-2 HPS Imperatortm Series - Wiring Schematic Drawings4143212 1346674 312558 HVL V1 243575V600V550V115V230V120V240V110V220V5 254323 24561116564213778L V2134HV56575V600V550V115V230V120V240V110 V220 VPH**AJ Schematic for 50, 75 and 100VA UnitsPH**AJ Schematic for 150VA to 1500VA Units High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse (Primary Volts) Links Between Terminals Connect To Clips To 600 575 550 None 1, 4 Unfused 600 575 550 None 6, 7 1-5, 4-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 120 115 110 3-4, 1-2 1, 4 Unfused 240 230 220 2-3 1, 4 Unfused 120 115 110 3-4, 1-2 4, 6 1-5 240 230 220 2-3 4, 6 1-5 High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse (Primary Volts)

2 Links Between Terminals Connect To Clips To 600 575 550 None 2, 5 Unfused 600 575 550 None 1, 6 2-7, 5-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 120 115 110 4-5, 2-3 2, 5 Unfused 240 230 220 3-4 2, 5 Unfused 120 115 110 4-5, 2-3 1, 5 2-7 240 230 220 3-4 1, 5 2-7 Page 2 of 9123412344 31267612438553 4212 134 HVL V230V460V240V480V220V440V115V230V120V240 V110V220 VPH**MQMJ Schematic for 50, 75 and 100VA Units High Voltage (HV) Install Supplied Links Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 240 230 220 1-2, 3-4 1, 4 Unfused 480 460 440 2-3 1, 4 Unfused 240 230 220 1-2, 3-4 6, 7 1-5, 4-8 480 460 440 2-3 6, 7 1-5, 4-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 120 115 110 3-4, 1-2 1, 4 Unfused 240 230 220 2-3 1, 4 Unfused 120 115 110 3-4, 1-2 4, 6 1-5 240 230 220 2-3 4, 6 1-5PH**MQMJ Schematic for 150VA to 1500VA Units High Voltage (HV) Install Supplied Links Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 240 230 220 2-3, 4-5 2, 5 Unfused 480 460 440 3-4 2, 5 Unfused 240 230 220 2-3, 4-5 1, 6 2-7, 5-8 480 460 440 3-4 1, 6 2-7, 5-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts)

3 Between Terminals Connect To Clips To 120 115 110 4-5, 2-3 2, 5 Unfused 240 230 220 3-4 2, 5 Unfused 120 115 110 4-5, 2-3 1, 5 2-7 240 230 220 3-4 1, 5 2-7234523451618773 24561564213L V213 4HV56213 456230V460V240V480V220V440V115V230V120V2 40V110V220 VHPS Imperatortm Series - Wiring Schematic Drawings continued123412344 31267612438553 4212 134 HVL **PG Schematic for 50, 75 and 100VA Units High Voltage (HV) Install Supplied Links Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 120 115 110 1-2, 3-4 1, 4 Unfused 240 230 220 2-3 1, 4 Unfused 120 115 110 1-2, 3-4 6, 7 1-5, 4-8 240 230 220 2-3 6, 7 1-5, 4-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 12 11 3-4, 1-2 1, 4 Unfused 24 23 22 2-3 1, 4 Unfused 12 11 3-4, 1-2 4, 6 1-5 24 23 22 2-3 4, 6 1-5 Page 3 of 9PH**PG Schematic for 150VA to 500VA Units High Voltage (HV) Install Supplied Links Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 120 115 110 2-3, 4-5 2, 5 Unfused 240 230 220 3-4 2, 5 Unfused 120 115 110 2-3, 4-5 1, 6 2-7, 5-8 240 230 220 3-4 1, 6 2-7, 5-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 12 11 4-5, 2-3 2, 5 Unfused 24 23 22 3-4 2, 5 Unfused 12 11 4-5, 2-3 1, 5 2-7 24 23 22 3-4 1, 5 2-72345234512135648773 2145616 HVL 2145623V24V22 VHPS Imperatortm Series - Wiring Schematic Drawings continuedPH**PG Schematic for 750VA and 1000VA Units High Voltage (HV)

4 Install Supplied Links Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 120 115 110 2-3, 4-5 2, 5 Unfused 240 230 220 3-4 2, 5 Unfused 120 115 110 2-3, 4-5 1, 6 2-7, 5-8 240 230 220 3-4 1, 6 2-7, 5-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 12 11 3-4, 1-2 1, 4 Unfused 24 23 22 2-3 1, 4 Unfused 123423452135648716 HVL V115V120V110V213564230V240V220V2 13423V24V22 VNote: secondary fuse clips not available on PH750PG or VDotted line representssupplied jumper **MLI Schematic for 50, 75 and 100VA Units High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 480 460 440 None 1, 3 Unfused 240 230 220 None 1, 7 Unfused 208 200 None 1, 2 Unfused 480 460 440 3-8 6, 4 1-5, 4-8 240 230 220 8-7 6, 4 1-5, 4-8 208 200 2-8 6, 4 1-5, 4-8 Low Voltage (LV) Install Supplied Jumpers Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 120 115 110 None 1, 4 Unfused 25 24 23 None 1, 3 Unfused 120 115 110 None 4, 6 1-5 25 24 23 None 3, 6 1-5 Page 4 of 9PH**MLI Schematic for 750VA and 1000VA Units26154324178 Dotted line representssupplied jumper VHV480V/460V/440V240V/230V/220V208V/200V 25V/24V/23V120V/115V/110V High Voltage (HV)

5 Install Supplied Jumpers Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 480 460 440 None 2, 6 Unfused 240 230 220 None 2, 4 Unfused 208 200 None 2, 3 Unfused 480 460 440 8-6 1, 5 2-7, 5-8 240 230 220 4-8 1, 5 2-7, 5-8 208 200 3-8 1, 5 2-7, 5-8 Low Voltage (LV) Install Supplied Jumpers Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 120 115 110 None 1, 4 Unfused 25 24 23 None 1, 2 Unfused Note: secondary fuse clips for 24V tap not available on the PH750 MLI or PH1000 MLI Imperatortm Series - Wiring Schematic Drawings continuedPH**MLI Schematic for 150VA to 500VA Units2615433421787 Dotted line representssupplied jumper VHV480V/460V/440V240V/230V/220V208V/200V 25V/24V/23V120V/115V/110V High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 480 460 440 None 2, 6 Unfused 240 230 220 None 2, 4 Unfused 208 200 None 2, 3 Unfused 480 460 440 8-6 1, 5 2-7, 5-8 240 230 220 4-8 1, 5 2-7, 5-8 208 200 3-8 1, 5 2-7, 5-8 Low Voltage (LV) Install Supplied Jumpers Load Lines Install Fuse (Secondary Volts)

6 Between Terminals Connect To Clips To 120 115 110 None 2, 4 Unfused 25 24 23 None 2, 3 Unfused 120 115 110 None 1, 4 2-7 25 24 23 None 1, 3 2-74143212 1346674 312558 HVL V1 **AR Schematic for 50, 75 and 100VA Units High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse (Primary Volts) Links Between Terminals Connect To Clips To 600 575 550 None 1, 4 Unfused 600 575 550 None 6, 7 1-5, 4-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 12 11 3-4, 1-2 1, 4 Unfused 24 23 22 2-3 1, 4 Unfused 12 11 3-4, 1-2 4, 6 1-5 24 23 22 2-3 4, 6 1-5 Page 5 of 9 HPS Imperatortm Series - Wiring Schematic Drawings continued5254323 24561116564213778L **AR Schematic for 150VA to 500VA Units High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse (Primary Volts) Links Between Terminals Connect To Clips To 600 575 550 None 2, 5 Unfused 600 575 550 None 1, 6 2-7, 5-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 12 11 4-5, 2-3 2, 5 Unfused 24 23 22 3-4 2, 5 Unfused 12 11 4-5, 2-3 1, 5 2-7 24 23 22 3-4 1, 5 2-7123412344 31267612438553 4212 134 HVL **QR Schematic for 50, 75 and 100VA Units High Voltage (HV) Install Supplied Links Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 240 230 220 1-2, 3-4 1, 4 Unfused 480 460 440 2-3 1, 4 Unfused 240 230 220 1-2, 3-4 6, 7 1-5, 4-8 480 460 440 2-3 6, 7 1-5, 4-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts)

7 Between Terminals Connect To Clips To 12 11 3-4, 1-2 1, 4 Unfused 24 23 22 2-3 1, 4 Unfused 12 11 3-4, 1-2 4, 6 1-5 24 23 22 2-3 4, 6 1-5PH**QR Schematic for 150VA to 500VA Units High Voltage (HV) Install Supplied Links Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 240 230 220 2-3, 4-5 2, 5 Unfused 480 460 440 3-4 2, 5 Unfused 240 230 220 2-3, 4-5 1, 6 2-7, 5-8 480 460 440 3-4 1, 6 2-7, 5-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 12 11 4-5, 2-3 2, 5 Unfused 24 23 22 3-4 2, 5 Unfused 12 11 4-5, 2-3 1, 5 2-7 24 23 22 3-4 1, 5 2-7234523451618773 24561564213L V213 4HV56213 6 of 9 HPS Imperatortm Series - Wiring Schematic Drawings continued123412344 31267612438553 4212 134 HVL V200V400V208V416V190V380V115V230V120V240 V110V220 VPH**SP Schematic for 50, 75 and 100VA Units High Voltage (HV) Install Supplied Links Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 208 200 190 1-2, 3-4 1, 4 Unfused 416 400 380 2-3 1, 4 Unfused 208 200 190 1-2, 3-4 6, 7 1-5, 4-8 416 400 380 2-3 6, 7 1-5, 4-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts)

8 Between Terminals Connect To Clips To 120 115 110 3-4, 1-2 1, 4 Unfused 240 230 220 2-3 1, 4 Unfused 120 115 110 3-4, 1-2 4, 6 1-5 240 230 220 2-3 4, 6 1-5123412344 31267612438553 4212 134 HVL V115V230V120V240V110V420V115V230V120V240 V110V220 VPH**PP Schematic for 50, 75 and 100VA Units High Voltage (HV) Install Supplied Links Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 120 115 110 1-2, 3-4 1, 4 Unfused 240 230 220 2-3 1, 4 Unfused 120 115 110 1-2, 3-4 6, 7 1-5, 4-8 240 230 220 2-3 6, 7 1-5, 4-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 120 115 110 3-4, 1-2 1, 4 Unfused 240 230 220 2-3 1, 4 Unfused 120 115 110 3-4, 1-2 4, 6 1-5 240 230 220 2-3 4, 6 1-5PH**SP Schematic for 150VA to 1000VA Units High Voltage (HV) Install Supplied Links Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 208 200 190 2-3, 4-5 2, 5 Unfused 416 400 380 3-4 2, 5 Unfused 208 200 190 2-3, 4-5 1, 6 2-7, 5-8 416 400 380 3-4 1, 6 2-7, 5-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 120 115 110 4-5, 2-3 2, 5 Unfused 240 230 220 3-4 2, 5 Unfused 120 115 110 4-5, 2-3 1, 5 2-7 240 230 220 3-4 1, 5 2-7234523451618773 24561564213L V213 4HV56213 456200V400V208V416V190V380V115V230V120V2 40V110V220 VPage 7 of 9 HPS Imperatortm Series - Wiring Schematic Drawings continuedPH**PP Schematic for 150VA to 1500VA Units High Voltage (HV) Install Supplied Links Supply Lines Install Fuse (Primary Volts)

9 Between Terminals Connect To Clips To 120 115 110 2-3, 4-5 2, 5 Unfused 240 230 220 3-4 2, 5 Unfused 120 115 110 2-3, 4-5 1, 6 2-7, 5-8 240 230 220 3-4 1, 6 2-7, 5-8 Low Voltage (LV) Install Supplied Links Load Lines Install Fuse (Secondary Volts) Between Terminals Connect To Clips To 120 115 110 4-5, 2-3 2, 5 Unfused 240 230 220 3-4 2, 5 Unfused 120 115 110 4-5, 2-3 1, 5 2-7 240 230 220 3-4 1, 5 2-7234523451618773 24561564213L V213 4HV56213 456115V230V120V240V110V220V115V230V120V2 40V110V220 VPH**MBMH Schematic for 100VA to 1500VA Units2615433421787 HVL VDotted line representssupplied jumper High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 600 575 550 None 2, 6 Unfused 480 460 440 None 2, 4 Unfused 240 230 220 None 2, 3 Unfused 600 575 550 8-6 1, 5 2-7, 5-8 480 460 440 4-8 1, 5 2-7, 5-8 240 230 220 3-8 1, 5 2-7, 5-8 Low Voltage (LV) Install Supplied Jumpers/ Load Lines Install Fuse (Secondary Volts) Links Between Terminals Connect To Clips To 120 115 110 None 2, 4 Unfused 100 95 90 None 2, 3 Unfused 120 115 110 None 1, 4 2-7 100 95 90 None 1, 3 2-71364723416585 HVL VDotted line representssupplied jumper **MBMH Schematic for 50 and 75VA Units High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse (Primary Volts)

10 Between Terminals Connect To Clips To 600 575 550 None 1, 3 Unfused 480 460 440 None 1, 7 Unfused 240 230 220 None 1, 2 Unfused 600 575 550 3-8 6, 4 1-5, 4-8 480 460 440 8-7 6, 4 1-5, 4-8 240 230 220 2-8 6, 4 1-5, 4-8 Low Voltage (LV) Install Supplied Jumpers/ Load Lines Install Fuse (Secondary Volts) Links Between Terminals Connect To Clips To 120 115 110 None 1, 4 Unfused 100 95 90 None 1, 3 Unfused 120 115 110 None 4, 6 1-5 100 95 90 None 3, 6 1-5 Page 8 of 9 HPS Imperatortm Series - Wiring Schematic Drawings continuedPH**MEMX Schematic for 50, 75 and 100VA Units High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse (Primary Volts) Between Terminals Connect To Clips To 415 None 1, 3 Unfused 400 None 1, 7 Unfused 380 None 1, 2 Unfused 415 3-8 6, 4 1-5, 4-8 400 8-7 6, 4 1-5, 4-8