Local Exhaust Ventilation Testing Protocols
National Institutes of Health Office of Research Services Division of Occupational Health and Safety Local Exhaust Ventilation Testing Protocols Technical Assistance Branch Reviewed June 2011 i National Institutes of Health Office of Research Services Division of Occupational Health and Safety Local Exhaust Ventilation Testing Protocols CONTENTS DOWNDRAFT SINKS FOR SMALL ANIMAL SURGERY ........................................ ................... 1 Introduction.
The measurement of air velocities is to be done using a calibrated thermoanemometer. For measurement purposes, the work surface of the downdraft sink is to be divided into an imaginary grid of four-inch squares. The air velocity measurements shall be taken at multiple points over the
Download Local Exhaust Ventilation Testing Protocols
Information
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document: