Example: barber
Local Exhaust Ventilation Testing Protocols

Local Exhaust Ventilation Testing Protocols

Back to document page

The measurement of air velocities is to be done using a calibrated thermoanemometer. For measurement purposes, the work surface of the downdraft sink is to be divided into an imaginary grid of four-inch squares. The air velocity measurements shall be taken at multiple points over the

  Measurement