Model KCT Automatic Transfer Switches MPAC …
Model KCT. Automatic Transfer Switches MPAC 1000t Controller Standard Features D Microprocessor controller D Real-time clock with battery backup D Broadrange voltage sensing (208--600 VAC) with 2%. accuracy on both sources D Frequency sensing with 1% accuracy on both sources D Environmentally sealed user interface D Keypad with tactile feedback pushbuttons D LED indicators D Selectable operating modes D Programmable inputs and outputs D Load/no load exercise function D Anti-single phasing protection D Load control inputs and outputs D Phase rotation sensing D Time-stamped event log D Gold-flashed engine start contacts D Modbusr communication with network and setup Ratings connections Voltage: 208--600 VAC 50/60 Hz MPAC 1000t Controller Current: 30--4000 amps Programmable Features Standard Contactor Features D System voltage and frequency D Open-transition operation with either Automatic or D Adjustable over/undervoltage and over/underfrequency for non- Automatic control the normal and emergency sources D 2, 3, or 4 poles D Adjustable time delays D Electrically operated, mechanically held D Commit/no commit Transfer D Double-throw, inherently interlocked design D ABC/BAC phase rotation selection with error detection (break-before-make power contacts) D Resettable historical data D Solid, switched, or overlapping neutral (make-before-break D In-phase m)
Automatic Transfer Switches Model KCT G11-80 (Model KCT Transfer Switch) 1/07o Page 1 Ratings Voltage: 208--600 VAC 50/60 Hz Current: 30--4000 amps