2015 International Plumbing code ( amended ). backflow /Cross-Connection Control Requirements amended SECTION NEW SECTION. NOTE: Sections highlighted yellow are sections of the 2015 IPC that were amended . The wording in the yellow sections include the amended language ( , if you compare Section below to that of the 2015 IPC, they will be different because the section below contains Louisiana amendments). Sections highlighted green are new sections added ( , there is no Section in the 2015 IPC as there is in this document, it was added to the Louisiana code via Louisiana amendments). Installation, inspection and testing of backflow prevention assemblies, barometric loops and air gaps.

312.10.2 Testing. Reduced pressure principle, double check, pressure vacuum breaker, reduced pressure detector fire protection, double check detector fire protection, and spill-resistant vacuum breaker backflow preventer assemblies shall be tested at the time of installation, immediately after repairs or relocation and at least annually.