Applications Considerations1 Introduction to ApplicationsThis section contains a few application questions that the product support teamhas answered quite frequently over the past several years. This section, by allmeans, is not totally inclusive; however, this information is extremely useful andwill be built upon in subsequent : Do you need a zone sensor on all IntelliPaks, whether ConstantVolume or Variable Air Volume (VAV)?Answer:Yes, all 20-130 ton units need a zone sensor, even a VAV unit. On a VAV unit,the zone sensor is used for the unoccupied, morning warm-up and daytimewarm-up modes. This is because the unit essentially operates constant volumein those modes and does not use the discharge air sensor. If none of thesemodes are being used, a fixed resistor of 10K (77 F), 1/4 watt, can be installedon 1TB4 terminals 1 and 2.
Applications Considerations 2 Typical Applications: This feature is commonly used with a fire alarm management system that will immediately shut down unit …
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
{{id}} {{{paragraph}}}
Fire Dampers and Smoke Dampers: The Difference, Safety Dampers Selection and Application, Safety Dampers Selection and Application Manual, Dampers, Fire Dampers, Fire Smoke Dampers, Smoke Dampers, Life Safety Dampers, Greenheck, Life Safety Dampers Life safety dampers, Fire, Smoke, Smoke Control Design and Activation, U.S.$Army$Corps$of$Engineers$ Air$Leakage$Test$Protocol$for$ Building$Envelopes$ Version3$A$May$11