Transcription of ARTICLE 240 - OVERCURRENT PROTECTION A. Installation
{{id}} {{{paragraph}}}
Reprinted with permission from NFPA 70-1968, the National Electrical Code , Copyright 1967, National Fire PROTECTION Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National Fire PROTECTION Association, on the referenced subject which is represented only by the standard in its entirety. National Electrical Code and NEC are registered trademarks of the National Fire PROTECTION Association, Inc., Quincy, MA 02269. ARTICLE 240 - OVERCURRENT PROTECTION A. Installation Scope. This ARTICLE provides the general requirements for the application of OVERCURRENT protective devices. 240-2. Purpose of OVERCURRENT PROTECTION . OVERCURRENT PROTECTION for conductors and equipment is provided for the purpose of opening the electric circuit if the current reaches a value which will cause an excessive or dangerous temperature in the conductor or conductor insulation.
240-6. Fuses. (a) Plug fuses and fuseholders shall not be used in circuits exceeding 125 volts between conductors except in circuits supplied from a system having a grounded neutral and no conductor in such circuits operating at more than 150 volts to ground. (b) Cartridge fuses and fuseholders rated at 300 volts shall