1 Water data 1) All second source domestic w ater c onnections require s epa rate a ccounts, meters and check valves at point of e ntry. 2) New Water s ervice(s) shall be activated by B oston Water a nd Sewer C ommission (BWSC) personnel after meter is installe d. In addition, when required, BWSC must ha ve a n approved as- built plan befor e a ctivation. 3) All taps must be direct taps. The only exception to this rule is when making a tap on a Water main that is 10 in diameter or smaller. In these instances the us e of a saddle will be permitted. 4) The c onnection of w ater services 4-inche s and larger shall be made using a t apping sleeve a nd va lve ( Muelle r Type H615 or e qual). 5) If the e xisting Water main is 6-inche s or l ess, any Water s ervice 4 -inche s or larger must be connected using 3- way branc h and a gate v alve. 6) If the building is mor e than 40 feet from the property line, a meter pit in the sidewalk may be required by the BWSC.
1 WATER DATA. 1) All second source domestic water connections require separate accounts, meters and check valves at point of entry. 2) New water service(s) shall be activated by Boston Water and Sewer Commission (BWSC)
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
{{id}} {{{paragraph}}}
Standard details for water main installations, Chicago, Water, PUBLIC WORKS STANDARD, STANDARD SPECIFICATION FOR STEAM BOILER INSTALLATIONS, Standard, Requirements for Electrical Installations – BS, Details, Polyethylene Water Service, SITE PLAN REVIEW CHECKLIST, AWWA C200 Steel Water Pipe, Industries, LLC