Transcription of CHAPTER 7 FIXED FIRE EXTINGUISHING INSTALLATIONS
{{id}} {{{paragraph}}}
CHAPTER 7 FIXED FIRE EXTINGUISHING INSTALLATIONS Key Changes Minor revision which incorporates the latest IMO SOLAS amendments and Circulars, and new EN / ISO standards for these systems/equipment. All amendments are highlighted in yellow. CHAPTER 1 FIXED FIRE EXTINGUISHING INSTALLATIONS .. 1 GENERAL .. 3 GAS INSTALLATIONS - 3 CARBON DIOXIDE SYSTEMS HIGH PRESSURE .. 4 Carbon dioxide Carbon dioxide storage 5 Distribution and release arrangements and test 6 Operating instructions and Installation 12 12 13 Exhaust ducts from galley 14 Deep fat cooking 15 CARBON DIOXIDE SYSTEMS LOW 16 16 Design 16 Installation 18 18 19 HALOGENATED HYDROCARBON SYSTEMS (HALON).
Carbon dioxide storage rooms 7.3.2.1 . The following requirements are applicable only for the storage rooms for fire-extinguishing media of fixed gas fire-extinguishing systems: .1 the storage room should be used for no other purposes; .2 if the storage space is located below deck, it should be located no