Information Class: PROPRIETARY CODE OF PRACTICE 101 FOR DISTRIBUTION SUBSTATION DESIGN Version 15 Issued By : Asset Management Department Asset Development Branch Date of Issue : 30 June, 2020 Code of PRACTICE No. 101 for DISTRIBUTION SUBSTATION Design Version 15 June 2020 Content - 1 Information Class: PROPRIETARY CODE OF PRACTICE 101 FOR DISTRIBUTION SUBSTATION DESIGN VERSION 15 CONTENTS Page 1. INTRODUCTION 1 2. OBJECTIVES 1 3. PROJECT MANAGEMENT 1 4. ELECTRICAL EQUIPMENT IN DISTRIBUTION SUBSTATION 2 5. ARCHITECTURAL/CIVIL DESIGN 6 6. VENTILATION DESIGN 23 7. LIGHTING DESIGN 25 8. ELECTRICAL SERVICES DESIGN 26 9. FIRE SERVICES DESIGN 28 10. CUSTOMER MAIN SWITCHROOM DESIGN 32 11. OUTDOOR SUBSTATION 36 12. PROVISION, INSTALLATION AND MAINTENANCE OF BUILDING 38 WORKS AND ACCESSORIES IN DISTRIBUTION SUBSTATION 13. DRAWINGS 43 APPENDIX A.
Code of Practice No. 101 for Distribution Substation Design Page 5 Version 15 June 2020 Information Class: PROPRIETARY 專有 4.4.2 The minimum dimensions of the transformer plinth should be 1.8m long x 1.35m wide and level with finished floor level. Actual plinth size is subjected to the transformer rating and type.