DIESEL GENERATOR OPERATION

Working Copy WP 04-ED1301. Revision 10. DIESEL GENERATOR OPERATION Technical Procedure EFFECTIVE DATE: 10/13/06. Leroy Bostick APPROVED FOR USE. CONTINUOUS USE PROCEDURE. Working Copy WP 04-ED1301 Rev. 10 Page 2 of 36. TABLE OF CONTENTS. INTRODUCTION.. 3. REFERENCES.. 3. PRECAUTIONS AND LIMITATIONS.. 4. INITIAL CONDITIONS.. 5. PERFORMANCE.. 6. DIESEL GENERATOR 1 OPERABILITY CHECK USING LOAD BANK. 25P-LB04/1.. 6. DIESEL GENERATOR 2 OPERABILITY CHECK USING LOAD BANK. 25P-LB04/1.. 13. REMOTE .. 21. LOCAL START.. 24. DIESEL GENERATOR LOADING.. 27. DIESEL GENERATOR OPERABILITY CHECK USING SUBSTATION.. 28. RESTORATION FOLLOWING OPERABILITY CHECK USING SUBSTATION.

operation, to prevent door from closing on personnel. 1.1.8 Verify water level in radiator expansion tank is greater than halfway in sight glass. NOTE FUEL RACK lever can also be used to EMERGENCY STOP diesel generator by manually placing lever in CLOSED position. 1.1.9 Verify FUEL RACK lever is in OPEN position.