Transcription of EJB, Style C Model M82 Series Junction Boxes …
{{id}} {{{paragraph}}}
INSTALLATIONWARNING1. Electrical power must be off before and duringinstallation and Field modification of this product is not permitted other thandrilled and tapped conduit entries per these EJB Series Junction Boxes are furnished with or withoutdrilled and tapped openings. Drilling and tapping of conduitopenings is subject to the limitations of maximum size and number of openings as well as spacings. Refer to DRILLINGAND TAPPING section following. All machining must bedone prior to Select a mounting location that will provide suitable strengthand rigidity for supporting all contained wiring and controldevices. Figure 1 shows the mounting dimensions for thefour detachable mounting Series Junction Boxes are used as a Junction box or pull box inrigid conduit Series Junction Boxes are suitable for use indoors or outdoors andare UL Listed and CSA Certified for Class I, Groups B, C, D; Class II,Groups E, F, G; and Class III hazardous (classified) areas as defined bythe National Electrical Code and the Canadian Electrical Code , andinclude a gasket to meet Type 4 watertight Series classified enclosures ordered with suffix -ATEX meet theATEX directive and are certified by ETL.
INSTALLATION WARNING 1. Electrical power must be off before and during installation and maintenance. 2. Field modification of this product is not permitted other than