ITR-20-007 ITER Electrical Design Handbook Earthing and Lightning Protection David Beltran 16 July 2020 ITR-20-007 ITER Electrical Design Handbook Earthing and Lightning Protection This work is licensed under the Creative Commons Attribution-Noncommercial-NoDerivs IGO-ported license. (CC BY-NC-ND IGO) You are free to share this work (copy, distribute and transmit) under the following conditions: you must give credit to the ITER Organization, you cannot use the work for commercial purposes and you cannot modify it. For a full copy of this license visit: ITR-20-007 Introduction Terminology & Acronyms Earthing and Lightning Protection ITR-20-007 Introduction 1 Introduction Abstract This manual is provided for the use of all Departments of the ITER Organization and is addressed to system specifiers, designers and users of Electrical components in otherwise non- Electrical plant systems.
Standard rated short- duration power-frequency withstand voltage kV (rms value) Standard rated lightning impulse withstand voltage kV (peak value) 7.2 20 40 60 24 50 95 125 145 36 70 145 170 72.5 140 325 245 (275) (325) 360 395 460 (650) (750) 850 950 1050