Transcription of Fisher FIELDVUE DVC2000 Digital Valve Controller
{{id}} {{{paragraph}}}
FIELDVUE DVC2000 Digital ValveControllerThis manual applies toInstrument LevelHC, AD, PDACD evice Type05F5 Device Revision11 Hardware Revision1 & 21 & 2 Firmware Revision1, 2, 3, 4 & 51, 2, 3, 4 & 5DD Revision31 ContentsSection 1 Introduction and , Electrical and Pneumatic Connections, and Basic Setup and of 2 Detailed Setup and Calibration viaHART Control the TagMessageDescriptorDateValve Serial NumberInstrument Serial NumberPolling AddressLUI LanguageW8755 Measured Variable Units and Input UnitsAnalog Input Range High and LowPressure UnitsTemperature UnitsActuator and Valve Supply PressureActuator StyleValve Serial NumberValve StyleZero Control SignalSetting SetDamping FactorExpert Tuning GainsInput CharacteristicCustom Characteristic TableSet Point Filter TimeLimits and CutoffsMinimum Opening and Closing TimeIntegral SettingsSetting Counter ManualD103176X012 DVC2000 Digital Valve ControllerJune 2017 Instruction ManualD103176X012 DVC2000
The DVC2000 digital valve controller can also be mounted on other actuators that comply with IEC 60534-6-1, IEC 60534-6-2, VDI/VDE 3845 and NAMUR mounting standards. Input Signal Analog Input Signal: 4-20 mA DC, nominal; split ranging available Minimum Voltage: Voltage available at instrument terminals must be 8.5 volts for analog control, 9.0