- 1 - foam SYSTEM SPECIFICATION WET PIPE AFFF SPRINKLER SYSTEM The sprinkler SYSTEM shall be a closed-head wet pipe AFFF foam water sprinkler SYSTEM designed to provide adequately proportioned foam water solution at listed water flows past proportioning device. SYSTEM shall be installed in accordance with NFPA 16, Standard for the Installation of Closed Head foam -Water Sprinkler Systems, NFPA 11, Standard for Low Expansion foam , NFPA 13, Standard for Installation of Sprinkler Systems and all other applicable codes or requirements. SYSTEM DEVICES SYSTEM Design (Insert Applicable SYSTEM Design.)
- 2 - Foam Concentrate Synthetic Aqueous Film Forming Foam (AFFF) or Alcohol Resistant Aqueous Film Forming Foam (AR-AFFF) shall be utilized. Water-soluble liquids shall be protected with Alcohol resistant type foam concentrate.