GENERAL: DESIGN GUIDELINES: A. Design General

CONSULTANT PROCEDURES & DESIGN GUIDELINES UNIVERSITY OF MISSOURI 232200 Steam and Condensate Piping and Pump Systems Revised 12/20/2013 Page 1 of 7 232100 General : Steam and condensate piping and pump systems included in this document are for building systems starting at the pressure reducing station (PRV). DESIGN GUIDELINES: A. DESIGN General 1. Definitions: Low pressure steam is 15 psig or less. High pressure steam is above 15 psig. 2. Campus Systems: MU: The steam distribution system operates at 60 psig and 400 F degrees. All equipment using campus steam must be capable of using steam at a temperature of 350F degrees. Confirm this with the Project Manager. Kansas City: Cooling Season: The steam distribution system operates as a single system at a common pressure of 10 to 15 psig. The system is supplied from one 300 hp boiler in Spencer Chemistry. Heating Season: The steam distribution system is decoupled at SMH 2.

check (bronze) or stainless steel disc check valves for pumping liquids of specific gravity of 0.65 and above. c) The pump shall contain a float operated snap-acting mechanism with no external seals or packing and stainless steel trim, and hardened stainless steel …