CONSULTANT PROCEDURES & DESIGN GUIDELINES UNIVERSITY OF MISSOURI 232200 Steam and Condensate Piping and Pump Systems Revised 12/20/2013 Page 1 of 7 232100 General : Steam and condensate piping and pump systems included in this document are for building systems starting at the pressure reducing station (PRV). DESIGN GUIDELINES: A. DESIGN General 1. Definitions: Low pressure steam is 15 psig or less. High pressure steam is above 15 psig. 2. Campus Systems: MU: The steam distribution system operates at 60 psig and 400 F degrees. All equipment using campus steam must be capable of using steam at a temperature of 350F degrees. Confirm this with the Project Manager. Kansas City: Cooling Season: The steam distribution system operates as a single system at a common pressure of 10 to 15 psig. The system is supplied from one 300 hp boiler in Spencer Chemistry.
Flanges 2 ½" and Larger Forged steel, Class 150, slip-on, per ANSI 16.5 . C ONSULTANT P ROCEDURES & D ESIGN G UIDELINES U NIVERSITY OF M ISSOURI 232200 Steam and Condensate Piping and Pump Systems Revised 12/20/2013 Page 7 of 7 232100 . VALVE TABLE . Service: Steam, up to 100 psi . ITEM SIZE DESCRIPTION . Gate 2" and Smaller Threaded, …