PDF4PRO ⚡AMP

Modern search engine that looking for books and documents around the web

Example: confidence

General Information Typical Pressure Sensing Line ...

(919) 460-5200 Sales Office: Cary, NC 27518 USA ASCO 2007 General InformationTypical Pressure Sensing line ConnectionFire Pump Controllers & Jockey Pump ControllersWATERSUPPLYFirePumpController FirePumpJockeyPumpControllerJockeyPumpFI RE PROTECTIONSYSTEMNFPA 20 (2007 Edition) Water Pressure Control. Unless the requirements of are met, there shall be provided a Pressure -actuated switch having adjustable high and low calibrated set points as part of the The requirements of shall not apply in a nonpressure-actuated controller, where the Pressure -actuated switch shall not be There shall be no Pressure snubber or restrictive orifice employed within the Pressure This switch shall be responsive to water Pressure in the fire protection The Pressure - Sensing element of the switch shall be capable of withstanding a momentary surge Pressure of 400 psi ( bar)

(919) 460-5200 • www.firetrol.com † Sales Office: Cary, NC 27518 USA ©ASCO 2007 General Information Typical Pressure Sensing Line Connection

Loading..

Tags:

  General, Information, Pressure, Line, Sensing, Typical, General information typical pressure sensing line

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Spam in document Broken preview Other abuse

Transcription of General Information Typical Pressure Sensing Line ...

Related search queries