Inspection and Testing Requirements for Fire …

Inspection and Testing Requirements for fire sprinkler Systems Semi- sprinkler Systems Monthly Quarterly annual Other annual Code NFPA 25. Inspection Gauges - Dry, Gauges on dry, preaction, and deluge systems PreAction & Deluge shall be inspected weekly to ensure that normal air and water pressures are being maintained. Gauges - Wet Pipe Gauges on wet pipe sprinkler systems shall be Systems inspected monthly to ensure that they are in good condition and that normal water supply pressure is being maintained. Control Valves (See "Valves" below). Alarm Devices Alarm devices shall be inspected quarterly to verify that they are free of physical damage. Hydraulic Nameplate The hydraulic nameplate, if provided, shall be inspected quarterly to verify that it is attached securely to the sprinkler riser and is legible. Buildings Annually, prior to the onset of freezing weather, buildings with wet pipe systems shall be inspected to verify that windows, skylights, doors, ventilators, other openings and closures, blind spaces, unused attics, stair towers, roof houses, and low spaces Hangers/Bracing sprinkler pipe hangers and seismic braces shall be inspected annually from the floor level.

Inspection and Testing Requirements for Fire Sprinkler Systems Sprinkler Systems Monthly Quarterly Semi-annual Annual Other Code NFPA 25 Inspection Gauges - Dry,

Tags:

  Annual, Testing, Requirements, Fire, Inspection, Sprinkler, Inspection and testing requirements for fire, Inspection and testing requirements for fire sprinkler, Annual annual

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Spam in document Broken preview Other abuse

Transcription of Inspection and Testing Requirements for Fire …

Related search queries