1K-90-9044 Effective: June 2014 Kidde ECS fire Suppression SystemComponent Description900 lb. Agent CylinderP/Ns 90-100900-001 and 90-100901-001 DESCRIPTIONK idde ECS System 900 lb. Agent Cylinders store sup-pression agent super-pressurized with dry nitrogen to360 PSIG at 70 F ( Mpa at 21 C). The cylinders arepainted red and are equipped with a 3-inch pressure dif-ferential valve, pressure gauge, optional liquid level indi-cator and optional low-pressure switch assembly. Thesafety burst disc is also located on the cylinder agent storage container discharges when the actua-tion assembly operates, causing the pressure differentialvalve to open. All of the Kidde actuators may be used toactuate the 900 lb. cylinder. The only exception is the48650001, which is not compatible with this container is installed in a vertical position with thevalve assembly pointing up. Interconnection to dischargepiping is 3-inch NPT. Interconnection can be via a 3-inchflex hose (P/N 06-118225-001) or via a suitably pressurerated groove style container is secured in place by a mounting bracket (P/N 236125), which must be fixed to a solid wall or strutassembly.