LABORATORY SAFETY DESIGN GUIDE 2014 EH&S LABORATORY SAFETY DESIGN GUIDE Revised July 2014 Page 2 of 74 TABLE OF CONTENTS Section 1 General Requirements for Laboratories Section 2 Environmental Requirements Section 3 LABORATORY Ventilation Section 4 Emergency Eyewash and SAFETY Shower Equipment Section 5 Compressed Gas and Cryogenic Components and Systems Section 6 Hazardous Materials Storage Cabinets Section 7 Biosafety Laboratories Section 8 Fire SAFETY Section 9 Additional Requirements for Radioactive Materials Laboratories Section 10 Additional Requirements for Laboratories with Irradiators and/or Radiation Producing Machines Section 11 Additional Requirements for Laboratories Using Non-Ionizing Radiation Sources Appendix A Additional Fume Hood Exhaust Criteria for Facilities Not Owned by the University of Washington Appendix B General Hazardous Materials Provisions Appendix C LABORATORY Decommissioning EH&S LABORATORY SAFETY DESIGN GUIDE Revised July 2014 Page 3 of 74 INTRODUCTION The construction of LABORATORY facilities requires oversight.
8. Provide shelf lips for seismic restraint. Lips should be ¾ inch above the shelf surface for bookshelves and 1 ½” inches above the shelf surface for shelves used to store breakable containers, chemicals, or other hazardous materials. 9. Refer to Chapter 11 of the Guide for design considerations for spaces containing Class 3B or 4 Lasers.