GEOTHERMAL TRAINING PROGRAMME Orkustofnun, Grensasvegur 9, Reports 2010 IS-108 Reykjavik, Iceland Number 7 29 main CONSIDERATIONS IN THE PROTECTION system DESIGN FOR A GEOTHERMAL POWER PLANT Luis A. Aguirre LaGeo de 15 Avenida Sur, Colonia Utila Santa Tecla, La Libertad EL SALVADOR ABSTRACT A proper PROTECTION system guarantees reliable and safe operation for a geothermal power plant. It is one of the most important factors during system engineering design and must be carefully selected to avoid equipment damage due to failures. The process design should include the selection of a PROTECTION scheme as well as adequate main and auxiliary equipment and installation CONSIDERATIONS .

Aguirre 32 Report 7 2.1.6 Generator rotor field protection The field circuit of a generator is an ungrounded system. A single ground fault will not generally