ELECTRIC SERVICE REQUIREMENTS REVISION PAGE 07/17//2012 METERING A METERING INSTALLATION REQUIREMENTS Table of Contents Section 300 PARAGRAPH PAGE METERING AND SERVICE ENTRANCE EQUIPMENT .. 1 GENERAL .. 1 METERED AND UNMETERED CONDUCTORS .. 1 SEALING OF METERS AND METERING 1 UNACCEPTABLE EQUIPMENT IN SEALED AREAS .. 2 METER LOCATION REQUIREMENTS .. 3 METER AND SERVICE LOCATIONS .. 3 PLANNING AND GROUPING FOR ADDITIONAL METERS .. 3 METER LOCATIONS - RESIDENTIAL .. 3 METER LOCATIONS - FACTORY-BUILT BUILDINGS/HOMES .. 3 RESIDENTIAL SERVICE - SINGLE DWELLING METER LOCATIONS .. 4 METER LOCATIONS - RESIDENTIAL MULTI-FAMILY BUILDINGS .. 5 METER LOCATIONS - COMMERCIAL AND INDUSTRIAL .. 5 UNACCEPTABLE METER LOCATIONS .. 5 WORKING SPACE (600 volts or less) .. BARRICADES/BARRIER POSTS .. 9 METER ROOM REQUIREMENTS .. 10 UNACCEPTABLE EQUIPMENT IN METER ROOMS.
Stud and wing-nut assembly, or sealing screws shall be used for sealing all removable panels and covers to compartments used for routing or terminating unmetered conductors. When a stud and wing-nut assembly is used for sealing, the stud shall be 1/4” x 20 (minimum).