UG-1: GeneralGreenbook038193 Page 1 of 22 Rev. #14: 12-17-20 Electric Distribution038193 Function:Asset Type:Issued by:Date:12-17-20 Rev. #14: This document replaces PG&E Document 038193, Rev. #13 For a description of the changes, see Page REQUIREMENTS FOR THE DESIGN AND INSTALLATION OFELECTRIC CONDUIT, INSULATED CABLE, AND FACILITIESP repared by: ABB1 DESIGN and ConstructionLisseth Villareal (LDV2)Purpose and ScopeThis document describes the MINIMUM REQUIREMENTS for the DESIGN and installation of electric conduits and pullinginsulated cables. This document also provides REQUIREMENTS of what facilities are allowed within the same Information1. A MINIMUM of 24 inches of cover for secondary (0 750 V) electric service, or 36 inches MINIMUM cover forprimary (over 750 V) is required.
G. Conduit, cable, and facilities installation must comply with the job design and construction documents. When deviation from the original design is required due to field conditions, the originating engineering department must be notified and will determine if the deviation will require additional Substructures. Follow the variance request ...