Transcription of Surge Arrester - System Voltage 2 kV to 245 kV
{{id}} {{{paragraph}}}
XPSS urge Arrester - System Voltage 2 kV to 245 kVXPS station class Silicone-Housed ArrestersMetal Oxide Surge Arrester XPS 2 Performance dataMaximum System voltages (Vm) - 245 kVrms Duty cycle rated voltages (Vr) 3 - 240 kVrms Classifying current (ANSI/IEEE) 10 kA peakDischarge current withstand strength: High current 4/10 s 100 kA peak Low current 2000 s 900 A peakEnergy capability: 2 impulses, (IEC CI. ) kJ / kV of MCOV Fullfi lls requirements of ANSI transmission-line discharge test for 245 kV systems Short-circuit / Pressure relief capability 65 kA rms sym Cantilever strength 20000 in - lbs / 2260 Nm Service conditions: Ambient temperature -50 C to + 45 C Design altitude 6000 ft / 1830 m Frequency 15 - 62 HzApplicationThe XPS polymer Arrester has been verifi ed to meet sta-tion class requirements of ANSI (IEEE Standard for Metal-Oxide Surge Arresters for AC Power Circuits).
Station Class Silicone-Housed Arresters XPS 3 Nameplate Direct-Molded Construction ABB’s type XPS surge arrester consists of high performance metal oxide disks molded in a shat-
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
{{id}} {{{paragraph}}}
POWER SYSTEMS, INC, Station Class, Station Class Surge Arresters, Station Class arresters, STATION CLASS SURGE, STATION CLASS SURGE ARRESTERS A. SYSTEM INFORMATION A-1 System Conditions, High Voltage Surge Arresters Station Class, Surge Arresters, Station, Class, Station-class surge arresters, Is a riser pole arrester, Arresters, Surge, Energy Products Division, Surge Arresters Application and Selection