Transcription of Troubleshooting Guide – Compressor Runs; No Cooling
{{id}} {{{paragraph}}}
Tr oubleshooting Guide Compressor runs ; No Cooling This situation could be the result of one of three main conditions: 1) System is low on refrigerant (undercharge/leak) or has an excess of refrigerant (overcharge). ) For guidance see our fact sheet Refrigerant R134a Charge Guidelines . 2) Compressor is damaged and unable to achieve sufficient differential pressures. This is highly unlikely and not to be considered at this stage. 3) There is a blockage somewhere in the refrigerant circuit. This is possible. Frigoboat systems employ a capillary tube (cap tube) metering device to separate the high and low pressure sides of the system. This is a very small tube that looks like a piece of copper wire and has a micro-bore in the center through which the liquid refrigerant is forced by the high pressure from the Compressor .
Troubleshooting Guide – Compressor Runs; No Cooling This situation could be the result of one of three main conditions: 1) System is low on refrigerant (undercharge/leak) or …
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
{{id}} {{{paragraph}}}
Advanced Troubleshooting Guide for Air Brake, COMPRESSOR, GUIDE, COMPRESSOR TROUBLE SHOOTING GUIDE, CRUISAIR MARINE A/C SYSTEMS TROUBLESHOOTING GUIDE, CRUISAIR ® MARINE A/C SYSTEMS TROUBLESHOOTING GUIDE, Troubleshooting Guide, TROUBLESHOOTING, Air Compressor Manual, AIR BRAKE, ROTARY SCREW AIR COMPRESSOR, ROTARY SCREW, AIR COMPRESSOR, Sullair, COMPRESSOR INSTALLATION OPERATION, COMPRESSOR INSTALLATION & OPERATION