EGVUSE09-07C_a EDUS 39 - 600 - F3. Engineering Data Engineering Data VRV Systems Basic Operation Guide Engi- AMERICAS. 1645 Wallace Drive, Suite 110. Carrollton, TX75006. 2007. DACA EGVUSE09-07C Daikin AC (AMERICAS), AMERICAS INC. Printed in 09/2007 K AK FS. DACA EGVUSE09-07C_a VRV Systems Basic Operation Guide 1. Explanations of P-H Diagram (Refrigerant Characteristics Table) .. 2. 2. Concept of Basic Refrigeration Cycle .. 3. 3. Points of Refrigerant Control of VRV System .. 4. Cooling 4. Heating Operation .. 5.
detected by thermistors on the liquid pipe and gas pipe, the indoor electronic expansion valve is regulated so as to put superheated degree at the evaporator outlet close to target value. * Superheated degree SH = (outdoor return-air pipe temperature - outdoor evaporating temperature)