{{id}} {{{paragraph}}}
PVI Industries, LLC Fort Worth, Texas WATER HEATER SIZING GUIDE FOR ENGINEERS COMMERCIAL INSTITUTIONAL INDUSTRIAL SIZING GUARANTEE PVI SIZING methods are guaranteed to be correct when used in accordance with the instructions as printed, as long as PVI equipment, with its unique performance characteristics, is used. If an installation should not have an adequate amount of hot WATER after proper use of the GUIDE , PVI will, at its cost, correct the installation to the engineer s satisfaction. COMMON FACTORS All calculated loads are converted to GPH (Gallons per Hour) 40 F to 140 F, or an 100 F rise. Appropriate conversion factors will be found near each formula.
1 Bath, Dish and Clothes Washer 4.9 2 Baths 5.0 2 Baths and Dishwasher 5.1 2 Baths and Clothes Washer 5.3 2 Baths, Dish and Clothes Washer 5.4 1 Bath 5.0 2 Baths 5.5 HOTELS AND MOTELS DIVERSITY FACTORS NUMBER UNITS* TU DIVERSITY FACTOR C 1-20 .98 21-40 .96 41-60 .94 61-80 .92 81-100 .89 ...