Back to document page

A CGS60C and a water heater are to be installed in a room measuring 6 ft - 3 in x 7 ft with an 8 ft ceiling. The water heater has an input of 30000 BTU/hr: Total input in thousands of BTU/hr = (172000 BTU/hr + 30000 BTU/hr)/1000 = 202 Volume of room = 6.25 ft x 7 ft x 8 ft = 350 ft3 350/202 = 1.73.