Transcription of Radio Powr SavrT Wireless Daylight Sensor
1 Radio Powr SavrTM LRFX-DCRB Wireless Daylight Sensor 369262i 1 Radio Powr SavrT Wireless Daylight Sensor The LutronR Wireless Daylight Sensor is a battery-powered Sensor that automatically controls lights via RF communication to compatible dimming or switching devices. This Sensor mounts to the ceiling and measures light in the space. The Sensor then transmits the light level to the associated dimming or switching devices that automatically control the lights to balance light level in the space. The Sensor combines both convenience and exceptional energy savings potential along with ease of installation. Features Wireless Daylight Sensor has simple calibration. Model Number Daylight compensation through LutronR reliable open LRFX-DCRB-WH. loop control. Color Code Designed to give a linear response to changes in Frequency / Channel Code viewed light level.
2 Light range 0 to 1600 lx (0 to 150 fc). Frequency / Channel Codes Uses Clear ConnectR technology. 2 = MHz ( , Canada, Mexico, Brazil). Works with Radio Powr SavrTM occupancy / vacancy 3 = MHz (Europe, ). sensors and Pico Wireless controls. 4 = MHz (China, Singapore). Intuitive test mode provides instant system verification. 5 = MHz (India). Multiple ceiling-mount methods available for different 6 = MHz (Japan). ceiling materials. 7 = MHz (Hong Kong, Macau). Front accessible test buttons make setup easy. 10-year battery life. Color Code RoHS compliant. WH = White Compatible RF Devices For use with Lutron products only. Communicates to various Wireless Lutron systems*. * Contact LutronR Customer Service at for frequency/channel code compatibility with your particular geographic region, and for integrating with other LutronR lighting and shading products.
3 S P E C I F I C AT I O N S U B M I T TA L Page 1. Job Name: Model Numbers: Job Number: Radio Powr SavrTM LRFX-DCRB Wireless Daylight Sensor 369262i 2 Specifications Regulatory Power / Performance Lutron Quality Systems Registered to ISO 9001:2008. Operating voltage: 3 V- Standards Operating current: 7 A. Requires one CR 2450 lithium battery LRF2- FCC certified 10-year battery life IC certified Non-volatile memory (settings are stored during COFETEL power loss). ANATEL. Enviroment ASEP. CRC Temperature: 32 F to 104 F (0 C to 40 C). SUBTEL For indoor use only SUPERTEL Relative humidity: < 90% non-condensing SUTEL. Meets CA ( ) Energy Commission Title 24 Range requirements LRF2-, LRF3-, LRF4-, LRF5-, LRF7- cULus Listed Local load controls must be located within 60 ft (18 m). LRF3- line of sight, or 30 ft (9 m) through walls, of a Sensor .
4 CE Marked (European Union) LRF6- TRA Type Approved (United Arab Emirates) Local load controls must be located within 23 ft (7 m). CITC (Kingdom of Saudi Arabia) through walls of a Sensor . LRF4- SRRC Type Approved (Mainland China). iDA Registered (Singapore). LRF5- Dimensions in WPC Type Approved (India) (17 mm). LRF6- . 007 YUUL0688. LRF7- FCC certified in (41 mm). S P E C I F I C AT I O N S U B M I T TA L Page 2. Job Name: Model Numbers: Job Number: Radio Powr SavrTM LRFX-DCRB Wireless Daylight Sensor 369262i 3 Mounting Installation Overview Location for average size areas Determine the Daylight Sensor mounting Arrow points towards the area viewed by the Sensor location using the diagrams at left: (towards windows). The arrow on the Daylight Sensor points toward the area viewed by the Sensor . Place the Daylight Sensor so the arrow is pointed at Bottom of Sensor the nearest window at a distance from the window of one to two times the effective window height (H).
5 The effective window height (H) starts at the window 1-2 H. sill or 3 ft (1 m) up from the floor, whichever is higher, H and ends at the top of the window. Ensure that the view of the Daylight Sensor is not 3 ft (1 m) obstructed ( ceiling fans or pendant fixtures). Do not position the Daylight Sensor above an electric H = Effective Window Height light that shines up at the ceiling or at the Sensor . Do not position the Daylight Sensor in the well of a skylight or above indirect lighting fixtures. Location for narrow areas For narrow areas where the Daylight Sensor cannot (corridors, private offices) be placed 1-2 (H) from windows, place Sensor near Arrow points towards the area viewed by the Sensor windows facing into the space. (away from window) Mount Sensor (s) away from large metal surfaces ( light fixtures or metal-backed ceiling tiles).
6 Metal Bottom of Sensor objects will affect the RF performance of the Sensor . For detailed and application specific mounting information, please see " Daylight Sensor Design and Application Guide" (P/N 3683587) at S P E C I F I C AT I O N S U B M I T TA L Page 3. Job Name: Model Numbers: Job Number.