GENERATOR SET. MOTOR STARTING . MOTOR STARTING . The following must be taken into account when motors are started while the load is on the GENERATOR set: Type of MOTOR Method of STARTING STARTING current requirement Voltage dip limitations Sequence in which the motors are started FORMULA. The GENERATOR set power is calculated as follows: kW gen = x MOTOR (output). MOTOR = MOTOR kW (output). MOTOR Where: MOTOR = MOTOR efficiency Created by J. M. J. lloyd Uncontrolled once printed DIRECT ON LINE ( ) STARTING . In STARTING the MOTOR is started with the windings connected in delta so full voltage is applied directly to the MOTOR terminals on start-up and during running. MOTOR STARTING CURRENT. A delta connected motors' STARTING current is 6 times its full load current.

Created by J. M. J. Lloyd Uncontrolled once printed STAR DELTA STARTING In Star Delta starting the motor is started with the windings connected in Star

Tags:

  Generators, Motor, Starting, Delta, Lloyd, Generator set motor starting

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of GENERATOR SET MOTOR STARTING - FG Wilson

1 GENERATOR SET. MOTOR STARTING . MOTOR STARTING . The following must be taken into account when motors are started while the load is on the GENERATOR set: Type of MOTOR Method of STARTING STARTING current requirement Voltage dip limitations Sequence in which the motors are started FORMULA. The GENERATOR set power is calculated as follows: kW gen = x MOTOR (output). MOTOR = MOTOR kW (output). MOTOR Where: MOTOR = MOTOR efficiency Created by J. M. J. lloyd Uncontrolled once printed DIRECT ON LINE ( ) STARTING . In STARTING the MOTOR is started with the windings connected in delta so full voltage is applied directly to the MOTOR terminals on start-up and during running. MOTOR STARTING CURRENT. A delta connected motors' STARTING current is 6 times its full load current.

2 ALTERNATOR OVERLOAD CAPACITY. The GENERATOR set alternators' overload capacity is times its rated output. FORMULA. The ratio of GENERATOR set kW to MOTOR kW is calculated as follows: kW gen x = 6 x MOTOR kWm m kW gen = 6 x MOTOR kWm x kW gen = times MOTOR KWm Created by J. M. J. lloyd Uncontrolled once printed STAR delta STARTING . In Star delta STARTING the MOTOR is started with the windings connected in Star so the STARTING voltage is reduced by 3. MOTOR STARTING CURRENT AND TORQUE. The STARTING current is reduced to 2 times its full load current The STARTING torque is reduced to 1/3 of the value FORMULA. The ratio of GENERATOR set kW to MOTOR kW is calculated as follows: kW gen = 2 x MOTOR kWm x kW gen = times MOTOR kWm Created by J.

3 M. J. lloyd Uncontrolled once print


Related search queries