SECTION 15183 - REFRIGERANT PIPING
www.abpenc.comASME Standard: Comply with ASME B31.5, "Refrigeration Piping." PART 2 - PRODUCTS 2.01 COPPER TUBE AND FITTINGS A. Drawn-Temper Copper Tube: ASTM B 280, Type ACR, clean, dry and capped. B. Annealed-Temper Copper Tube: ASTM B 280, Type ACR, clean, dry and capped. Annealed copper tubing shall not be used for piping larger than 0.625 O.D. 15183 - 3