Example: dental hygienist

1/2-6 HP Air-cooled Condensing Units

1/2-6 HPAir- cooled Condensing UnitsTechnical GuideModels LZ | LH | LSLK-HTSTB | MAY 2018 Replaces LK-HTSTB | JAN 20182 Table of ContentsNomenclature ..2 Features & Benefits ..4 Hermetic Compressor Models ..5-11 Performance Data ..5-9 High Temperature (R- 404a /R-507A) ..5 Extended Temperature (R- 404a /R-507A) ..6 Low Temperature (R- 404a /R-507A) ..7 Extended Temperature (R-407C) ..8 Extended Temperature (R-448A/R-449A) ..9 unit Specifications and AWEF Ratings ..10 Electrical Data ..11 Scroll Compressor Models ..12-31 Performance Data ..12-27 Medium Temperature (R- 404a /R-507A) ..12-13 Medium Temperature (R-407A)..14-15 Medium Temperature (R-407C).

6 Extended Temperature R-404A/R-507A PERFORMANCE DATA: HERMETIC COMPRESSOR MODELS Model Compressor Capacity BTUH @ 90°F Ambient by SST 30°F 25°F 20°F 0°F -10°F -20°F …

Tags:

  Unit, 404a, Cooled, Condensing, Hp air cooled condensing units, R 404a

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 1/2-6 HP Air-cooled Condensing Units

1 1/2-6 HPAir- cooled Condensing UnitsTechnical GuideModels LZ | LH | LSLK-HTSTB | MAY 2018 Replaces LK-HTSTB | JAN 20182 Table of ContentsNomenclature ..2 Features & Benefits ..4 Hermetic Compressor Models ..5-11 Performance Data ..5-9 High Temperature (R- 404a /R-507A) ..5 Extended Temperature (R- 404a /R-507A) ..6 Low Temperature (R- 404a /R-507A) ..7 Extended Temperature (R-407C) ..8 Extended Temperature (R-448A/R-449A) ..9 unit Specifications and AWEF Ratings ..10 Electrical Data ..11 Scroll Compressor Models ..12-31 Performance Data ..12-27 Medium Temperature (R- 404a /R-507A) ..12-13 Medium Temperature (R-407A)..14-15 Medium Temperature (R-407C).

2 16-17 Medium Temperature (R-448A/R-449A) ..18-19 Low Temperature (R- 404a /R-507A) ..20-21 Low Temperature (R-407A/R-407F) ..22-23 Low Temperature (R-407C) ..24-25 Low Temperature (R-448A/R-449A) ..26-27 unit Specifications ..28 AWEF Ratings ..28 Electrical Data ..30-31 Semi-Hermetic Compressor Models ..32-35 Performance Data ..32-33 Medium Temperature (R- 404a /R-507A) ..32 Low Temperature (R- 404a /R-507A) ..33 unit Specifications and AWEF Ratings ..34 Electrical Data ..35 Replacement Parts by InterLink ..36 Dimensional Drawings ..37-38 Nomenclature CHTX30L6 CFModelCompressorApplicationComp.

3 HPTemperature RefrigerantVoltageIdentifierL= LarkinH = HermeticT = OutdoorX = LG05 = 1/2 HPH = High - R- 404a /R-507A, B = 208-230/1/60F = StockS = Semi-HermN = IndoorO = Copeland08, 09 = 3/4 HPM = Med. Temp. R-407A/F, R-407C, C = 208-230/3/60Z = ScrollS = Beacon II010, 011 = 1 HPL = Low Temp. R-448A/R-449AD = 460/3/6001* = 1 1/2 HPE = Extra Low = 230/1/6002* = 2 HPX = Extended = 230/3/6003* = 3 HP04* = 4 HP05* = 5 HP060 = 6 HP3 Features & BenefitsTypical Outdoor Hermetic UnitTypical Outdoor unit with throwaway liquid-line filter and sight glassTypical Outdoor Hermetic unit with liquid filter drier and sight glassQuality All Units are completely leak tested in a helium environment, bump tested and allowed to cycle off on the high and low pressure control.

4 Each unit has a copy of the run data shipped inside the electrical panel Electrical circuits are completely checked for continuity Piping is laid out to minimize stress and vibration and is pre-bent to eliminate leaks Encapsulated, auto-reset, high and low pressure controls to eliminate leaks (standard on all high and medium temperature models, adjustable low pressure control standard on low temperature models)ComponentsFan Specifically matched with motor and coil to attain maximum air movement and coolingMotor Rated for 50 and 60 cycle application Standard PSC or optional Variable Speed EC (VSEC) motors with Orbus ControllerCompressor Wide variety of compressors including: hermetic, semi-hermetic and scroll.

5 R- 404a /R-507A available for both medium and low temperature applications (R-407A/R-407C available on select Scroll & Hermetic Models, and R-448A/R-449A available on select Scroll & Hermetic Models) Spring-mounted compressors with vibration eliminators on all 1-1/2 to 3 HP semi-hermetic compressors; 1/2 to 1 HP semi-hermetic compressors are rigid mounted and have a discharge loop Discharge service valves come standard on all Units Serviceability Suction service valves for hermetic and scroll compressors located outside the cabinet for quick installations. Semi-hermetic compressor models have a suction valve on the compressor and an access fitting on the suction line entering the cabinet.

6 Receiver with fusible plug, liquid shutoff valve and charging port is standard Large electrical panel for ease of access Prefabricated wiring harnesses for tight crimp connections and consistent labeling unit stays on if the hood is removed for servicing Sight glass is easily viewableCabinet & Construction Microchannel coil technology standard on most Units Painted steel cabinets for superior strength and corrosion protection Heavy duty steel raised base with 1-1/2 legs Fan guards and wiring conduit on indoor models41/2 - 6 HP Condensing unit : OptionsElectrical OptionsMechanical OptionsThe Beacon II Refrigeration System is a preassembled, factory installed refrigeration system featuring an integrated microcomputer based electronic control Beacon II Refrigeration System replaces the expansion valve, solenoid valve, room thermostat, defrost control and timer.

7 It comes factory preset, thereby eliminating all of the expensive and time consuming fine tuning and adjustments necessary for a good system installation. For additional information, contact your Sales Representative. OptionOutdoorIndoorStockAdjustable low pressure control for medium temp. or electric defrost timer onlyOptionOption1/2-3 HP low II OptionOptionN/ACrankcase heaterStandardN/AStandardDual pressure control (not available on Beacon II )OptionOptionN/AElectric defrost with timer & contactors (040-060 models only)OptionOption4-6 HP low fan cycling pressure or temperature (2 fan Units ) (Pressure standard on Beacon II )OptionOptionN/AFused disconnect / Non-fused disconnectOptionShipped looseN/APhase loss / low voltage monitorOptionOptionN/ASmart Defrost Kit (Factory-Installed)OptionOptionN/AVariab le speed EC (VSEC)

8 Motors with Orbus controller OptionN/AN/AOptionOutdoorIndoorStock12" Extended legs for snowbelt operationShipped looseShipped looseShipped looseHead pressure control flooding valveStandardOptionStandardLiquid line drier, sight glassOptionOptionStandardLiquid line solenoid valve and pumpdown switchOptionOptionN/ALow ambient kit with heated and insulated receiver, TD relayOptionN/AN/AOil separator with discharge line check valve (D cabinet)OptionOptionN/AOversize receiver (D cabinet)OptionOptionN/APrecharged refrigerant with quick connect fittingsOptionOptionN/AReplaceable core liquid line filter (D cabinet)OptionOptionN/AReplaceable core suction line filter (D cabinet)OptionOptionN/ASuction accumulatorOptionOptionN/ASuction line filterOptionOptionN/A5* = T for Outdoor, N for Indoor, S for Beacon II = RST compressor not suitable for R-507 NOTES:High Temperature R- 404a /R-507 APERFORMANCE DATA.

9 HERMETIC COMPRESSOR MODELSM odelCompressorCapacity BTUH @ 90 F Ambient by SST40 F35 FLH*005H6 RST45C1E8,9108,150LH*009H6 RST64C1E12,52011,570LH*010H6 RST70C1E13,72012,610LH*015H6CS10K6E21,40 019,460LH*025H6CS14K6E26,32024,270LH*032 H6CS20K6E42,89039,110 ModelCompressorCapacity BTUH @ 95 F Ambient by SST40 F35 FLH*005H6 RST45C1E8,5107,790LH*009H6 RST64C1E11,98011,080LH*010H6 RST70C1E13,01011,960LH*015H6CS10K6E20,26 018,400LH*025H6CS14K6E25,00023,030LH*032 H6CS20K6E40,73037,110 ModelCompressorCapacity BTUH @ 100 F Ambient by SST40 F35 FLH*005H6 RST45C1E8,1207,430LH*009H6 RST64C1E11,44010,580LH*010H6 RST70C1E12,31011,320LH*015H6CS10K6E19,12 017,350LH*025H6CS14K6E23,69021,810LH*032 H6CS20K6E38,56035,100 ModelCompressorCapacity BTUH @ 110 F Ambient by SST40 F35 FLH*005H6 RST45C1E7,3406,710LH*009H6 RST64C1E10,3509,580LH*010H6 RST70C1E10,92010,040LH*015H6CS10K6E16,88 015,280LH*025H6CS14K6E21,10019,410LH*032 H6CS20K6E34,21031,0706 Extended Temperature R- 404a /R-507 APERFORMANCE DATA: HERMETIC COMPRESSOR MODELS* = T for Outdoor, N for Indoor, S for Beacon II = RST compressor not suitable for R-507 NOTES.

10 ModelCompressorCapacity BTUH @ 90 F Ambient by SST30 F25 F20 F0 F-10 F-20 F-25 FLH*005X6 RST45C1E6,8506,2705,7103,6902,8101,9801, 550LH*008X6 RST55C1E8,1307,4506,7904,4303,4902,7102, 400LH*009X6 RST64C1E9,5908,8208,0805,3504,2403,2702, 850LH*010X6 RST70C1E10,0609,3008,6605,5404,0802,7502 ,050LH*015X6CS10K6E16,43015,09013,5507,9 105,2803,6102,970LH*020X6CS12K6E18,59017 ,00015,4209,1106,3304,0303,270LH*025X6CS 14K6E20,15018,63017,27010,9008,0505,7404 ,760LH*030X6CS18K6E29,49027,03024,55014, 39010,6007,3806,180LH*032X6CS20K6E32,420 29,62026,84015,93012,2008,7807,000 ModelCompressorCapacity BTUH @ 95 F Ambient by SST30 F25 F20 F0 F-10 F-20 F-25 FLH*005X6 RST45C1E6,5305,9705,4403,5102,6601,8501, 430LH*008X6 RST55C1E7,7307,0706,4404,1803,2802,5502, 250LH*009X6 RST64C1E9,1508,4207,7105,0904,0203,1002, 690LH*010X6 RST70C1E9,4008,8508,1705,1203,7702,6101, 820LH*015X6CS10K6E15,40013,96012,8007,22 05,0603,3302,630LH*020X6CS12K6E17,49016, 00014,4708,3705,8303,8602,830LH*025X6CS1 4K6E18,92017,49016,25010,0907,5305,2304, 330LH*030X6CS18K6E27,84025,49023,13013,4 809,7106,7505,620LH*032X6CS20K6E30,53027 ,89025,24014,80011,2007,9306,220 ModelCompressorCapacity BTUH @ 100 F Ambient by SST30 F25 F20 F0 F-10 F-20 F-25 FLH*005X6 RST45C1E6,2005,6705,1703,3302,5101,7201, 310LH*008X6 RST55C1E7,3206,7006,0903,9303,0702,3902, 100LH*009X6 RST64C1E8,7208,0107,3404,8303,8102.