Example: confidence

1756 ControlLogix Communication Modules Specifications ...

Technical Data1756 ControlLogix Communication Modules SpecificationsStandard ControlLogix Catalog Numbers 1756 -CN2, 1756 -CN2R, 1756 -CNB, 1756 -CNBR, 1756 -DNB, 1756 -DHRIO, 1756 -DH485, 1756 -EN2F, 1756 -EN2T, 1756 -EN2TP, 1756 -EN2TR, 1756 -EN3TR, 1756 -EN2 TSC, 1756 -ENBT, 1756 -EWEB, 1756 -RIO, 1756 -SYNCH, 1756 -TIME ControlLogix 1756 Communication Module Conformal Coated Catalog Numbers 1756 -CN2RK, 1756 -EN2TK, 1756 -EN2 TPK, 1756 -EN2 TRK, 1756 -TIMEKC ontrolLogix-XT Catalog Numbers 1756 -CN2 RXT, 1756 -DHRIOXT, 1756 -EN2 TXT, 1756 -EN2 TRXT, 1756 -EN2 TPXTTo picPageAdditional Resources2 New and Updated Information2 Available Communication Modules3 ethernet /IP Network4 Stratix Switches14 ControlNet Network15 DeviceNet Network23DH+ and Remote I/O Networks26DH-485 Network32 SynchLink Communication34 Time Synchronization362 Rockwell Automatio

EtherNet/IP Network Specifications For these requirements Select this interface Control I/O modules and drives Act as an adapter for I/O on remote EtherNet/IP links Communicate with other EtherNet/IP devices (messages and HMI) Bridge EtherNet/IP links to route messages to devices on other networks 1756-EN2F, 1756-EN2FK 1756-EN2T, 1756-EN2TK ...

Tags:

  Ethernet, 1756

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 1756 ControlLogix Communication Modules Specifications ...

1 Technical Data1756 ControlLogix Communication Modules SpecificationsStandard ControlLogix Catalog Numbers 1756 -CN2, 1756 -CN2R, 1756 -CNB, 1756 -CNBR, 1756 -DNB, 1756 -DHRIO, 1756 -DH485, 1756 -EN2F, 1756 -EN2T, 1756 -EN2TP, 1756 -EN2TR, 1756 -EN3TR, 1756 -EN2 TSC, 1756 -ENBT, 1756 -EWEB, 1756 -RIO, 1756 -SYNCH, 1756 -TIME ControlLogix 1756 Communication Module Conformal Coated Catalog Numbers 1756 -CN2RK, 1756 -EN2TK, 1756 -EN2 TPK, 1756 -EN2 TRK, 1756 -TIMEKC ontrolLogix-XT Catalog Numbers 1756 -CN2 RXT, 1756 -DHRIOXT, 1756 -EN2 TXT, 1756 -EN2 TRXT, 1756 -EN2 TPXTTo picPageAdditional Resources2 New and Updated Information2 Available Communication Modules3 ethernet /IP Network4 Stratix Switches14 ControlNet Network15 DeviceNet Network23DH+ and Remote I/O Networks26DH-485 Network32 SynchLink Communication34 Time Synchronization362 Rockwell Automation Publication 1756 -TD003K-EN-E - August 20171756 ControlLogix Communication Modules SpecificationsAdditional ResourcesThese documents contain additional information concerning related products from Rockwell Automation.

2 You can view or download publications at To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales and Updated InformationThis table contains the changes made in this Modules Installation Instructions, publication ENET-IN002 Provides information on installing ethernet /IP Secure Communication User Manual, publication ENET-UM003 Provides information on system architecture, configuring secure Communication , and Modules Installation Instructions, publication CNET-IN005 Provides instructions for installing ControlNet System User Manual, publication 1756 -UM001 Provides information on system architecture, configuring secure Communication , and Time Synchronization Module - Series B User Manual, publication 1756 -UM542 Describes the functionality, installation, configuration, and operation of the 1756 -TIME Network Configuration User Manual, publication DNET-UM004 Provides information on system architecture, configuring Communication , and DH-485 Communication Module User Manual.

3 Publication 1756 -UM532 Provides information on system architecture, configuring Communication , and Data Highway Plus-Remote I/O Communication Interface Module User Manual, publication 1756 -UM514 Provides information about programming, messaging, applying, and connecting the SynchLink Module User Manual, publication 1756 -UM521 Provides information about topologies, configurations, planning, and installing a Synchlink Automation Wiring and Grounding Guidelines, publication general guidelines for installing a Rockwell Automation industrial Certifications website, declarations of conformity, certificates, and other certification picPageAdded Conformal Coating Catalog Numbers, for example, the K in the catalog number, 1756 -TIMEK, indicates that the module has the conformal coating option.

4 The K catalog numbers are listed on the front page but are not listed in corresponding product Radiated RF Immunity specification: 3V/m with 1 kHz sine-wave 80% AM from MHz where PCE boilerplate specification and certification Automation Publication 1756 -TD003K-EN-E - August 201731756 ControlLogix Communication Modules SpecificationsAvailable Communication ModulesNetworkCat. bridge, fiber, 256 Logix connections71756-EN2 TEtherNet/IP bridge, copper, 256 Logix connections71756-EN2 TSCE therNet/IP secure Communication module71756-EN2TR, 1756 -EN2 TRKE therNet/IP bridge, embedded switch, copperSupports as many as 8 axis of motion71756-EN3 TREtherNet/IP bridge, embedded switch, copperSupports as many as 128 axis of motion71756-EN2TP, 1756 -EN2PK, 1756 -EN2 PXTE therNet/IP bridge with Parallel Redundancy ProtocolSupports as many as 8 axis of motion71756-ENBTE therNet/IP bridge, copper.

5 128 Logix connections71756-EWEBE thernet web server, 128 Logix connections, Class 3 messaging only71756-EN2 TXTC ontrolLogix-XT , ethernet /IP bridge, copper, 256 Logix connections71756-EN2 TRXTC ontrolLogix-XT ethernet /IP bridge module with embedded switch7 ControlNet1756-CN2/B, 1756 -CN2/C, 1756 -CN2R/B, 1756 -CN2R/C, 1756 -CN2 RKControlNet bridge, 128 Logix connections(1)(1)128 connections are available for standard use. An additional three connections are reserved for redundant , 1756 -CNBRC ontrolNet bridge, 64 connections; recommend using only Logix connections for I/O151756-CN2 RXTC ontrolLogix-XT, ControlNet bridge, 128 Logix connections(1)

6 19 DeviceNet1756-DNB/EDeviceNet bridge23 Data Highway Plus 1756 -DHRIOData Highway Plus/Remote I/O module271756-DHRIOXTC ontrolLogix-XT, Data Highway Plus/Remote I/O module29 Remote I/O1756-DHRIOData Highway Plus/Remote I/O module271756-RIO/BRemote I/O module271756-DHRIOXTC ontrolLogix-XT, Data Highway Plus/Remote I/O module29DH-485 module1756-DH485DH-485 module32 SynchLink 1756 -SYNCHS ynchLink fiber-optic Communication link34 Time Synchronization1756-TIMETime synchronization on different interfaces by using Global Positioning System (GPS) technology364 Rockwell Automation Publication 1756 -TD003K-EN-E - August 20171756 ControlLogix Communication Modules SpecificationsCommunication ConnectionsA ControlLogix system uses connections to establish Communication links between devices.

7 The types of connections include the following : Controller-to-local I/O Modules or local Communication Modules Controller-to-remote I/O or remote Communication Modules Controller-to-remote I/O (rack-optimized) Modules Produced and consumed tags Messages Controller access with the Studio 5000 environment Controller access with RSLinx software for HMI or other applicationsYou indirectly determine the number of connections the controller uses by configuring the controller to communicate with other devices in the system. The limit of connections ultimately resides in the Communication module you use for the connection.

8 If a message path routes through a Communication module, the connection that is related to the message also counts towards the connection limit of that Communication NetworkThe ethernet Industrial ( ethernet /IP) network protocol is an open industrial-networking standard that supports both real-time I/O messaging and message exchange. The ethernet /IP network uses off-the-shelf ethernet Communication chips and physical you need toSelect this interfaceControl I/O Modules and drivesAct as an adapter for I/O on remote ethernet /IP linksCommunicate with other ethernet /IP devices (messages and HMI)Bridge ethernet /IP links to route messages to devices on other networks 1756 -EN2F bridge1756-EN2T bridge1756-EN2TP bridge1756-EN2 TPXT bridge1756-EN2TR bridge1756-ENBT bridgeSupport device level ring (DLR)

9 And linear topologies1756-EN2TR, 1756 -EN2 TRK redundant bridge1756-EN3TR, 1756 -EN2 TRK redundant bridgeSupport for Parallel Redundancy Protocol1756-EN2TP bridge, 1756 -EN2 TPXT bridge, 1756 -EN2 TPK PRP bridgeProvide PRP control in environments where temperatures range from C ( F) 1756 -EN2 TPXT bridgeProvide control in environments where temperatures range from C ( F) 1756 -EN2 TXT bridgeSupport device level ring (DLR) and linear topologiesProvide control in environments where temperatures range from C ( F) 1756 -EN2 TRXT redundant bridgeSecure access to a control system from within the plant network1756-EN2 TSC bridgeUse an Internet browser to remotely access tags in a ControlLogix controllerCommunicate with other ethernet /IP or generic ethernet devices (messaging only.)

10 No I/O control)Bridge ethernet /IP links to route messages to devices on other networks 1756 -EWEB, 1756 -EWEBK web server1756-EN2 TRXT bridge1756-EN2 TPXT bridgeRockwell Automation Publication 1756 -TD003K-EN-E - August 201751756 ControlLogix Communication Modules SpecificationsEtherNet/IP Network SpecificationsTable 1 - ControlLogix ethernet /IP Connections Specifications (1)(1)Includes the K conformal coating catalog Unconnected Messages (backplane + ethernet ) TCPCIP(2)(2)CIP connections can be used for all explicit or all implicit applications. For example, a 1756 -ENBT module has a total of 128 CIP connections that can be used for any combination of + 641756-EN2F128256128 + 1281756-EN2T128256128 + 1281756-EN2 TXT128256128 + 1281756-EN2TP128256128 + 1281756-EN2 TPXT128256128 + 1281756-EN2TR128256128 + 1281756-EN2 TRXT128256128 + 1


Related search queries