alarmline DIGITALL inear heat Detection SystemKidde alarmline Digital linear heat Sensor is a twin conductor cable withtemperature-sensitive insulation protected by a special braid, PVC orfluoropolymer outer sheath to meet specific application requirements. Thisconcept of point-of-risk detection can also be employed as cabling forelectrical fire alarm systems - subject to British Standards or customerspecification a cable and detector in one,installed close to potential sources offire, alarmline Digital cable provideseconomical detection for a wide rangeof risks which include: Rack storage Vehicle engine bays Floating roof fuel storage tanks Turbines Boiler fronts Ships holds Rail locomotives and rolling these risks fall well withinAlarmline Digital cable'scontinuous operating ambientlimits of -65 C to +200 of handling and stripping of thecable permits quick installation andallows conventional or proprietarymethods of support to be type cable clips should not beused.

ALARMLINE DIGITAL Linear Heat Detection System 3 Kidde Fire Protection UK Sales Office – Head Office Thame Park Road, Thame, Oxfordshire OX9 3RT

Tags:

  Linear, Data, Heat, 3 alarmline d data 081102, Alarmline, 081102, Linear heat

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 3-Alarmline D Data 081102 - KIDDE

1 alarmline DIGITALL inear heat Detection SystemKidde alarmline Digital linear heat Sensor is a twin conductor cable withtemperature-sensitive insulation protected by a special braid, PVC orfluoropolymer outer sheath to meet specific application requirements. Thisconcept of point-of-risk detection can also be employed as cabling forelectrical fire alarm systems - subject to British Standards or customerspecification a cable and detector in one,installed close to potential sources offire, alarmline Digital cable provideseconomical detection for a wide rangeof risks which include: Rack storage Vehicle engine bays Floating roof fuel storage tanks Turbines Boiler fronts Ships holds Rail locomotives and rolling these risks fall well withinAlarmline Digital cable'scontinuous operating ambientlimits of -65 C to +200 of handling and stripping of thecable permits quick installation andallows conventional or proprietarymethods of support to be type cable clips should not beused.

2 Care must be taken to avoidmechanical impact, kinking,unacceptable heat sources or otherfactors which may affect the integrityof the cable. Twin-conductor switching heatsensing cable Effective monitoring at precise pointof risk Economical, reliable and durabledetection Simple and easy to install Applied where other types of firedetection are unsuitableOperationAlarmline Digital cable operates byshort-circuiting in a fire condition orwhere acceptable operatingtemperature levels are exceeded, toprovide a quick, positive and Digital may be used as astand-alone detection facility with asensor open circuit FAULT or shortcircuit FIRE condition, monitored by anassociated simple electrical an integral part of a fire protectionsystem, alarmline Digital cable may beused as a conventional detector andoperate automatic extinguishingsystems via an Extinguishing ControlPanel (ECP).

3 See KIDDE FIREPROTECTION datasheet DIGITALL inear heat Detection System2 For details of sensor supports consultKidde Fire Protection data sheet E9832-409 " alarmline linear Detection -Sensor Supports".WARNING: alarmline Digital cablesmust never be connected to mainselectrical UnitsKidde Fire Protection manufactures arange of Firebeta II ConventionalControl Units from 2 to 12 zones ofdetection, including a range ofExtinguishing Control Panels (ECP). data sheets are available on request,or from our National Power category "A"approval granted to26794-2 Factory Mutual USA approvalgranted to all alarmline DigitalCable CEA European Approval Testing oncable type 26794-1xx/H8040confirms compliance withrequirements of Class 3 pointdetectors when installed 25mmbelow a ceiling, perpendicular tothe air flow (BS 5445 Part 5:1977and EN54 Part 5 refers).Ordering DataAlarmline Digital cables are availablein lengths of 50 metres, 100 metres,and then 100 metre increments up to1000 metres.

4 The last three digits ofthe cable reference denote the length, D5387-068-100 specifies arequirement for 1000m of : Refer to table on Page 3 for PartNumber lengths of cable may be joinedby crimp connectors, using a crimpingtool to achieve longer sensor No. 27426-601 - Crimp ConnectorCONDUCTORT innedcopper-coveredsteelAlarmline DigitalCable ConstructionSHEATHB lack or coloured PVC,thermoplastic strip braidor fluoropolymerINSULATIONT emperature-sensitivethermoplastic orfluoropolymerALARMLINE DIGITALL inear heat Detection System3 KIDDE Fire ProtectionUK Sales Office Head OfficeThame Park Road, Thame, Oxfordshire OX9 3 RTTel: +44 (0)1844 265003. Fax: +44 (0)1844 256156. E-mail: Web: Sales OfficeUnit 12, Atley Way, North Nelson Industrial Estate, Cramlington, Northumberland NE23 1 WATel: +44 (0)1670 713455. Fax: +44 (0)1670 735553 International OfficesDubai: Tel: +971 4 337 2498.

5 Fax: +971 4 337 5088 Hong Kong: Tel: +852 2195 3688. Fax: +852 2743 7477 Singapore: Tel: +65 424 7979. Fax: +65 424 7978 Australia: Tel: +61 3 9765 3850. Fax: +61 3 9765 3800 KIDDE Fire ProtectionSpecification subject to change without 11/02 SpecificationAll cablesTinned copper-covered steelConductor diameter conductor resistance(per km at 20 C)100 ohmsVoltage Rating100V DCInsulation MaterialTemperature sensitive to thicknessInner CoresH8028, H8040, H8040N, H8045, H8045N: each two cores (red, black) twinned together: diaH8069: two cores (black, black and white) twinned together: diaH9650: two cores (white, black) twinned together: diaOuter SheathH8028: PVC (black): diaH8069: PVC (red): diaH8040: Polythene braid (red with green ID tracer): diaH8040N: (black nylon) diaH8045: Polythene braid (red with black ID tracer): diaH8045N: (black nylon) diaH9650.

6 Fluoropolymer (white) diaPart AppropriateApplicationAmbient ( C)Alarm ( C)Alarm ( C)Detection time(small flame)D5387-068H80404561704 secondsInternal onlyB6794-100H8040N4561704 secondsInternal/ExternalD5387-085H804570 79905 secondsInternal onlyB6794-101H8045N7079905 secondsInternal/ExternalD5387-105H802870 9711310 secondsInternal/ExternalD5387-170H806910 517819020 secondsInternal/ExternalD5387-227H965020 021623820 secondsInternal/External