Transcription of 3M Self-Regulating Heat Tracing Cables
1 Division des produits lectriquesCompagnie 3M Canada 5757 London, ON N6A 4T11408-01605-F 3M, 2014. Tous droits r serv s. Imprim au Canada. 3M TTS, HSX et KSR sont des marques de commerce de 3M, utilis es sous licence au Self-Regulating heat Tracing Cablesfor Commercial BuildingsPLEASE NOTE: The diagrams and instructions outlined in this guide are for illustration purposes only. They are not necessarily to scale and do not necessarily represent exact real-world heat Tracing systems. In addition, they are not meant or implied to be a replacement for a licensed professional. Any use of 3M heat Tracing Cables must be in accordance with all local regulations and/or building codes.
2 Please consult your local authority. Contents13M Self-Regulating Heating CablesConstruction & ..2 Properties ..2 Advantages ..2 Construction ..33M Self-Regulating Heating Cables Ordering Information & Materials Guide:Pipe Freeze Protection Ordering Information (TTS cable )..4 Pipe Freeze Protection Materials Guide (TTS cable ) ..6 Roof & Gutter Snow & Ice Melting Ordering Information (TTS cable ) ..15 Roof & Gutter Snow & Ice Melting Materials Guide (TTS cable ) ..17 Surface Snow & Ice Melting Ordering Information (KSR cable ) ..25 Surface Snow & Ice Melting Materials Guide (KSR cable ) ..27 Hot Water Temperature Maintenance Ordering Information (HSX cable ).
3 36 Data Sheets:TTS Pipe Freeze Protection DATA Sheet ..37 TTS Roof & Gutter Snow & Ice Melting DATA Sheet ..40 KSR Surface Snow & Ice Melting DATA Sheet ..41 HSX Hot Water Temperature Maintenance DATA Sheet ..42 Accessories ..43 Introduction:3M Canada and Thermon Manufacturing Company have entered into a strategic alliance to market the commercial line of heat Tracing products manufactured by Thermon. The alliance agreement provides 3M Canada exclusive rights within Canada to sell and market three distinct products: TTS , KSR , and HSX heat Tracing Cables and :These heat Tracing Cables consist of a conductive-polymer heating matrix extruded between two parallel copper bus conductors.
4 heat is generated in the conductive polymer matrix when energized. The bus conductors provide uniform voltage across the heating matrix by providing current down the entire length of the cable . The conductive polymer matrix is irradiated with an electron beam to provide cross-linking and lock in performance the temperature increases, the electrical paths in the carbon-polymer heating matrix become longer and the resistance of the heating element increases. This causes the heat output of the cable to decrease. As the temperature of the heating matrix increases, the resistance of the heating matrix increases. This is a Self-Regulating heat Tracing Cables can adjust their output to the surrounding tem-perature down the cable length.
5 This adaptability to individual thermal conditions provides more heat where needed and can also reduce energy consumption as the ambient temperature increases, reducing heating : Self-Regulating heat output at any point Cut-to-length at any point down the cable No overheating Can overlap heating cable Economical, simple installation Safe assembly due to simple handling Low investment Reliable, long term performance2 Construction & Function3M Self-Regulating Heating Cables3M Self-Regulating heat Tracing Cables consist of a conductive-polymer heating matrix between two parallel bus conductors. Therefore the cable can be cut to any desired length without changing its heating matrix provides an infinite number of parallel resistances.
6 This provides the ability of the heating cable to respond to temperature conditions at any point down its length and adjust its heat grounding braid serves as a safety conductor and provides a continuous ground outer protective jacket protects against corrosion, chemicals, and adverse environmental Self-Regulating Heating Cables3 Construction:Construction & FunctionTTS Self-Regulating Heating Cablefor Pipe Freeze ProtectionDescription:Cut-to-length TTS Self-Regulating heating Cables are designed to provide freeze protection to metallic and non-metallic piping. Whether the application is a small project or a complex network, designing an electric heat trace system is easy with TTS heating refer to the TTS materials guide for Pipe Freeze Protection on page 8 of this catalogue for full heating Cables are are approved for use in ordinary (non-classified) and hazardous (classified) of Application.
7 Freeze protection or low temperature maintenance Metallic or non-metallic piping tanks and equipment Sewage pipes, intake and drain lines (external Tracing only) Water meters and outside pipes/taps Water pipes in unheated areas Sprinkler systems Refrigeration * For pipe freeze protection add thermal insulation for a complete installation Ratings:Available watt , 26, 33 w/m @ 10 C (5, 8, 10 w/ft @50 F) Supply or 208-240 Vac Max. Maintenance C (150 F) Max. Continuous exposure temperature Power 85 C (185 F) Minimum installation C (-60 F) Minimum bend 32 mm ( ") 85 C (185 F)4 Certifications / Approvals:Canadian Standards Association Ordinary (Non-Classified) Locationss Hazardous (Classified)
8 Locations Class I, Division 2, Groups A, B, C and D Class II, Division 2, Groups F and G Meets or exceeds - IEEE 515, - UL 1588 CSA InformationTTS Self-Regulating Heating Cablefor Pipe Freeze Protection5T923456781 Ref # Part Number Description 1 TTS-5-1-OJ 5 W/FT @ 120V 1 TTS-8-1-OJ 8 W/FT @ 120V 1 TTS-10-1-OJ 10 W/FT @ 120V 1 TTS-5-2-OJ 5 W/FT @ 240V 1 TTS-8-2-OJ 8 W/FT @ 240V 1 TTS-10-2-OJ 10 W/FT @ 240V cable Termination Kits 2 18-SXG-KIT1 Power Connection Gland Kit w/o Junction Box 2 ECA-1-SR-SP Metallic Power Connection Kit with Junction Box 4 ECT-2-SR Metallic T-Splice Kit with Junction Box 2 PCA-1-SR Non-metallic Power Connection Kit with
9 Junction Box 4 PCS-1-SR Non-metallic T-Splice Kit with Splice Cover 1 8 HS-PBSK Inline heat Shrink Splice Kit (Under Insulation) 4 HS-TBSK T-Splice heat Shrink Kit (Under Insulation) 5 ET-6C End Termination Kit (Ordinary & Div 2 Approved) Installation Accessories 6 BTape Binding / Attachment Tape (1/2" X 60 yds) 7 CL Caution Labels (25 Per Pack) 9 AL TAPE 3M Aluminum Tape (2" X 180') for non-metallic pipe Controls 3 R1-050-DP Indoor Thermostat 3 R3C-0120-DP Weatherproof Indoor / Outdoor ThermostatOrdering InformationBasic Components:A pipe freeze protection system that uses TTS heating cable will typically include heating cable and components shown in the illustration and TTS ordering information table below.
10 1 Junction box appropriate for the application to be supplied by the Self-Regulating Heating Cablefor Pipe Freeze Protection6 Materials GuideContentsIntroduction ..7 Creating a Materials List Step 1: Establish Parameters ..8 Step 2: Select the Proper TTS Heating cable ..9 Step 3: Determine TTS Circuit Lengths ..11 Step 4: Choose TTS Installation Accessories ..12 Tips ..13 Thermostatic Control ..14 TTS Self-Regulating Heating Cablefor Pipe Freeze ProtectionIntroduction:While an insulated pipe can withstand cold temperatures longer than an uninsulated pipe, the contents of the pipe will cool to the temperature of the surrounding environment.