Example: marketing

A11 Series Low Temperature Cutout Controls …

Refer to the QuickLIT website for the most up-to-date version of this Series Low Temperature Cutout Controls product BulletinA11 Series low Temperature Cutout Controls are available with Single-Pole, Single-Throw (SPST) or Single-Pole, Double-Throw (SPDT) contact action. Typical applications include the sensing of low Temperature conditions to avoid over cooling or icing of hydronic coils, cooling coils, and liquid-handing pipes. The Controls are compact and sturdy, and have an adjustable Temperature setpoint range with a fixed differential.

A11 Series Low Temperature Cutout Controls Product Bulletin 2 Overview The A11 controls are compact and sturdy and feature an adjustable range with a fixed differential.

Tags:

  Product, Control, Temperatures, Bulletin, Low temperature cutout controls, Cutout, Low temperature cutout controls product bulletin

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of A11 Series Low Temperature Cutout Controls …

1 Refer to the QuickLIT website for the most up-to-date version of this Series Low Temperature Cutout Controls product BulletinA11 Series low Temperature Cutout Controls are available with Single-Pole, Single-Throw (SPST) or Single-Pole, Double-Throw (SPDT) contact action. Typical applications include the sensing of low Temperature conditions to avoid over cooling or icing of hydronic coils, cooling coils, and liquid-handing pipes. The Controls are compact and sturdy, and have an adjustable Temperature setpoint range with a fixed differential.

2 The range adjustment screw is accessible at the bottom of the control , and at the top of the control when the cover is removed. Figure 1: A11 Series Low Temperature Cutout ControlTable 1: Features and BenefitsFeaturesBenefitsPrecision Repeat AccuracyRemains unaffected by ambient Temperature at the control diaphragm cup and 4 ft ( m) capillary (20 ft [ m] sensing bulb must be in the controlled area).Trip-Free Manual ResetAllows the lever to reset. You must press and release the lever before operation Snap-Acting Contacts in a Dust Protected EnclosureEnables the A11 to operate to the fullest Reading ScaleProvides easy to adjust setpoint.

3 Adjustments can be made from the top or bottom of the Series Low Temperature Cutout ControlsProduct BulletinA11A, A11B, A11D, A11 ECode No. LIT-125010 Issued April 2018A11 Series Low Temperature Cutout Controls product Bulletin2 OverviewThe A11 Controls are compact and sturdy and feature an adjustable range with a fixed differential. The range adjustment screw is accessible at the bottom of the control or at the top, when the cover is removed. A factory-set low Temperature stop is available when 2 shows the A11 dimensions.

4 Figure 2 describes the A11 electrical ratings. Table 2: Electrical RatingMotor Rating120 V208 V240 VMotor DescriptionAC Full Load Locked Rotor Duty - 125 VA, 24 to 277 Mounting 2: A11 Series Low Temperature Cutout Controls Dimensions, in. (mm)A11 Series Low Temperature Cutout Controls product Bulletin3 Ordering InformationTable 3 describes the A11 Series Low Temperature Cutout control models. When ordering an A11 Series Low Temperature Cutout control :1. Specify the product Specify the low Temperature Cutout stop setting, if and ReplacementsIf the A11 Series Low Temperature Cutout control fails to operate within its specifications, replace the unit.

5 Contact your nearest Johnson Controls Specifications Table 3: A11 ModelsModelDescriptionA11 ASingle-Pole, Single-Throw (SPST), Open Low, Manual ResetA11 BSPST, Open Low, Automatic RecycleA11 DSingle-Pole, Double Throw (SPDT), Manual ResetA11 ESPDT, Automatic RecycleA11 Low Temperature Cutout ControlsProduct CodesA11A: SPST, Open Low, Manual ResetA11B: SPST, Open Low, Automatic RecycleA11D: SPDT, Manual ResetA11E: SPDT, Automatic RecycleRange Cutout35 to 45 F (2 to 7 C)DifferentialA11A and A11D: Temperature must be 12 F ( C) above Cutout point before control can be and A11E: 12 F ( C)Ambient TemperatureMinimum: 0 F (-18 C)Maximum: 140 F (60 C)Maximum Temperature at Bulb250 F (121 C)Sensing Element1/8 in.

6 X 20 ft ( mm x m) or 1/8 in. x 40 ft ( mm x m)Capillary Length4 ft ( m)SwitchSnap-acting contacts in dust-protected enclosureMaterialCase: ( mm) Cold Rolled SteelCover: in. ( mm) Cold Rolled SteelFinishGalvanized SteelConduit Opening22 mm ( in.) hole for mm (1/2 in.) conduitMounting BracketStandard on all controlsShipping WeightIndividual Pack: lb ( kg)Overpack of 20 Units: 38 lb (17 kg)Electrical RatingPilot Duty: 125 VA, 24 to 277 VACM otor RatingsAC Full Load Ampere: 120 V = A, 208 V = A, 240 V = AAC Locked Rotor Ampere: 120 V = A, 208 V = A, 240 V = ANon-Inductive Ampere.

7 120 V = A, 208 V = A, 240 V = APublished in Series Low Temperature Cutout Controls product Bulletin4 Johnson Controls and PENN are registered trademarks of Johnson Controls in theUnited States of America and/or other countries. All other trademarks used herein are the propertyof their respective owners. Copyright 2018 by Johnson Controls . All rights Technologies & Solutions507 E. Michigan Street, Milwaukee, WI 53202 ComplianceUnited StatesUL Listed, File SA516, SDFYFCC Compliant to CFR 47, Part 15 Subpart B, Class ACanadaUL Listed, CSA Class No.

8 1222 01, File LR948 Industry Canada, ICES-003 The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls , Inc. shall not be liable for damages resulting from misapplication or misuse of its Low Temperature Cutout Controls


Related search queries