AGT Constant Voltage Transformers - AEL Group

AGT Constant Voltage TransformersAGT Constant Voltage Transformers (CVTs) areideal maintenance free solutions for loads that cansuffer erratic operation or be damaged by electricalnoise (common or series mode), local transients,mains power sags, surges and Voltage Transformer (CVT)Galvanic IsolationHigh common and normal mode noiseattenuationSag, surge and brownout protectionSine wave output (regardless of inputwaveform)Low installation and running costs(maintenance free)High Mean Time Between Failure (MTBF), over200,000 hours ( years)Easy to installOperationUsing a Constant Voltage Transformer (CVT), aninput Voltage variation of +/-15% is automaticallystabilized to within +/-3% of nominal on the faced with an extreme transient such as alocal lightning strike, the CVT will present a

AGT Constant Voltage Transformers Applications Medical Equipment requiring separation from the mains supply EN 60601 and Isolated Power Systems (IPS)

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of AGT Constant Voltage Transformers - AEL Group

1 AGT Constant Voltage TransformersAGT Constant Voltage Transformers (CVTs) areideal maintenance free solutions for loads that cansuffer erratic operation or be damaged by electricalnoise (common or series mode), local transients,mains power sags, surges and Voltage Transformer (CVT)Galvanic IsolationHigh common and normal mode noiseattenuationSag, surge and brownout protectionSine wave output (regardless of inputwaveform)Low installation and running costs(maintenance free)High Mean Time Between Failure (MTBF), over200,000 hours ( years)Easy to installOperationUsing a Constant Voltage Transformer (CVT), aninput Voltage variation of +/-15% is automaticallystabilized to within +/-3% of nominal on the faced with an extreme transient such as alocal lightning strike, the CVT will present a lowimpedance to the mains protecting both itself andany connected loads.

2 The Constant VoltageTransformer generates a perfect sine wave outputeven when fed from square or quasi-square 15000VA for large industrial loadsOptionsAny nominal Input/Output up to 660 VacMains Voltage and frequency to suit geographiclocationPlug and socket or terminal versions availableas standardParallel and Series operation for enhancedreliability and larger power ratings. Contact oursales team for further designs with multiple AC and/or DCoutputsFor sizes above 15 KVA 1000VA - all standard units come with a baseplate for ease of fixingOutstanding Spike and Electrical NoiseProtectionProviding unparalleled reliability and conditioningperformance, spikes and electrical noise areneutralised with attenuation as high as 75dB.

3 Inaddition the input and output transformer windingsare physically separated (Galvanic Isolation), thisseparation ensures that there is no connectionbetween the mains supply and the load. A CVTtherefore provides an impenetrable barrier tospikes and high frequency electrical noise. Thisbarrier also works in reverse to prevent a noisy load from polluting the mains Mode NoiseCommon mode NoiseSuperior Sag, Surge and BrownoutProtectionMains Voltage Sags and Surges of as much as50% are automatically corrected by a CVT.

4 A CVTwill ride through most brownouts or mains dipsbecause of its resonant long as at least 30% of the normal supplyvoltage is present a suitably selected CVT canprovide adequate power for your critical Electronics Limited. Advance Park, Wrexham. LL14 3YR United KingdomSales: 01978 821 000 in England and Wales 1742090. An AEL Group CompanyAGT Constant Voltage TransformersApplicationsMedical Equipment requiring separation fromthe mains supply EN 60601 and IsolatedPower Systems (IPS)Industrial PLCs and process controlapplicationsWeighbridgesGrid link applications and G5/4 Rail signalling and critical systemsSensitive Electronic test systemsAutomatic Sine-wave GenerationFerro-resonant transformer technology ensuresthat each power conditioner will always generatea pure stable sine-wave even when fed from apolluted mains or distorted square-wave = InputB = OutputLoad regulationOutput Voltage regulated to within 5%.

5 Overloadsdrag the output Voltage down, and a completeshort circuit shuts down the CVT with no of the short circuit restores the outputwith no Switched Mode Power Supply(SMPS) DriverFerro-resonant transformer technology alsoprovides waveform shoulder-lifting. A CVT is themost efficient way to drive a switched mode powersupply (SMPS). Input surges are reducedprolonging life and conduction times arelengthened. In addition the CVT providesharmonic buffering and improved reservoircapacitor hold up for the inevitable supply micro-breaks, which occur with grid protection Electronics Limited.

6 Advance Park, Wrexham. LL14 3YR United KingdomSales: 01978 821 000 in England and Wales 1742090. An AEL Group CompanyModel NoPower RatingVA x D x H mmNet WeightKg (approx)ConnectionsSingle phaseAGT 100*100146 x 185 x 1908 Terminals orPlug and SocketAGT 250*250183 x 230 x 19013 AGT 450*450183 x 250 x21018 AGT 650*650183 x 280 x 21022 AGT 1000*1000183 x 320 x 21033 AGT 1300*1300265 x 500 x 28537 AGT 1600*1600265 x 500 x 28542 AGT 2000*2000265 x 590 x 28563 AGT 2500*2500265 x 590 x 28572 Single phaseAGT 3000*3 KVA405 x 637 x 45589 TerminalsAGT 4000*4 KVA405 x 637 x 455100 AGT 5000*5 KVA405 x 637 x 610133 AGT 7000*7 KVA405 x 637 x 610168 AGT 8000*8 KVA405 x 637 x 765194 AGT 10000*10 KVA405 x 637 x 765202 AGT 12500* KVA405 x 637 x 920223 AGT 15000*15 KVA405 x 637 x 920243 Three

7 Phase ATT 9000*9 KVA650 x 1325 x 773410 TerminalsATT 12000*12 KVA650 x 1325 x 773485 ATT 15000*15 KVA650 x 1325 x 773530 ATT 18000*18 KVA650 x 1325 x 773575 ATT 21000*21 KVA650 x 1325 x 773680 ATT 24000*24 KVA650 x 1325 x 773745 ATT 30000*30 KVA650 x 1325 x 773785 ATT 37500* KVA650 x 1325 x 773864 ATT 45000*45 KVA650 x 1325 x 773864* suffix assigned on Voltage and connection choice ATT three phase CVTs are star output and CANNOT be used to power DELTA loads